Specifications
DS300f G2 Series User Manual
179
Figure 6 - 6: Number 2 Cooling Unit with Cache Backup Battery (BBU) LED indicating battery failure
replaCInG a CaChe baCkup battery
The cache backup battery, also called a Battery Backup Unit (BBU) powers the cache to preserve data that has
not been written the physical drives. The battery is attached to the top of the Cooling Unit assembly. Each Cooling
unit has one battery.
To replace a backup battery, swap out the Cooling Unit with the BBU that needs replacement. Follow the
instructions in "Replacing a Cooling Unit" on page 178.
Red or amber BBU
LED indicates a battery
problem
Cautions
Try reconditioning the battery before you replace it. See "Reconditioning a Battery" on page
<?> or "Reconditioning a Battery (CLU)" on page <?>.
The battery assembly is replaced as a unit. Do not attempt to disconnect the battery by itself.
Installing the wrong replacement battery can result in an explosion.
Dispose of used batteries according to the instructions that accompany the battery.
While the battery is removed, your system is vulnerable to data loss if the power fails while
data is being written to the logical drives.
If power service has failed, do not remove the battery if the RAID controller’s dirty cache LED
is ashing. See "Controller LEDs" on page <OV>.
Important
DO NOT remove a Cooling Unit unless there is a replacement available and on hand. Removing a
singleCoolingUnitwithoutreplacingitrightawaywilladverselyaffectairowwithintheenclosure
resulting in critical overheating and shutdown of the enclosure.