Brochure
HVAC-E-16
rev0519
• Ceiling (1)
• Aspen Mini Tank Pump (2)
• Cassette Unit (3)
• 1) Threaded rod
• 2) Wall mounted
• 3) Floor mounted
• 4) Placed in drip tray
TYPICAL PUMP LOCATIONS
❶
❸
❶
❷
❸
❹
• Pump Length - 8.25"
• Pump Width - 3.5"
• Pump Height - 2.7"
• Capacity - 8 GPH @ 0' Head / 1.6 GPH @ 49'
Head
• Max BTUs - 137,850
• Max Head in Feet - 49
• Max Temperature - 40°C/104°F
• Max Suction Lift - NA
• Sound Level - 35dB(A)
• Dry Contact Rating - 3A NC
• Voltage - 230v
• Amperes - 3 Max
• Watts - 46
• Integrated Reservoir - Yes
• Plenum Rated - No
• Cord Length - (1.5m) 5ft
• Reservoir Capacity - (0.24L) .063gal
SPECIFICATIONS
Head GPH BTU
0 8 137850
5 6.3 108450
10 5.2 90000
15 4.5 77500
20 3.8 66500
25 3.2 54600
30 2.8 48000
35 2.4 42000
40 2 34000
45 1.7 29250
49 1.6 27500
Mini Tank Pump 230v 60Hz
0
10
20
30
40
50
60
1.3 2 2.7 3.4 4.1 4.8 5.5 6.2 6.9 7.6 8.3
Head (ft)
Flow Rate (GPH)
Mini Tank Pump 230v 60Hz
230v 60Hz
KEY FEATURES
• High performance piston technology
• Included anti-siphon device
• Quiet operation
• High lift capacity
• Great alternative to large and noisy traditional
condensate pumps
• Ideal for ceiling cassette ducted A/C units
• Can be used in conjunction with OEM lift pump
(if unit is fitted with one)
• Perfect for units without a lift pump
• Integrated overflow protection
• Mini Tank pump (including hard wired 1.5m
power cable) 5ft
• 2 Rubber adaptors (21.5mm & 31mm)
.84in & 1.2in
• Anti-siphon device
• Fixing kit
• Install manual
• 1 AMP fuse
IN THE BOX
❷