User Guide
12
13
Installation – Drain Hose, Pump & Wiring
Instalación – Manguera de Drenaje,
Bomba y Cableado
CONFIRM MAIN POWER SUPPLY IS ISOLATED. Thread power cable through evaporator to terminate
at incoming power terminal. Connect power and overflow alarm wires according to relevant diagram
and attach warning label to front of terminal cover. DO NOT USE A SEPARATE 115 or 230 VOLT
OUTLET TO POWER PUMP AS THIS IS NOT FAIL SAFE AND MAY CAUSE AN OVERFLOW.
WIRING: 1. Check that pump voltage conforms with evaporator voltage and that actual voltage
supplied is sufficient to drive pump. 2. Wire pump power cable to incoming power terminals in
evaporator so pump is permanently energized regardless of evaporator operation. 3. Connect
supplied inline fuse (1 amp) into one of the incoming power wires to pump. 4. Connect high level/
overflow alarm, by removing communication wire from condenser from it’s terminal in evaporator and
connecting it to gray wire from pump with a wirenut (or crimped butt connector where mandated). 5.
Connect purple wire to communication terminal in evaporator. This will prevent unit from operating in
case of blockage or pump failure. Note this circuit can carry a maximum of 5 amps. If external alarm is
required, connect N/O orange wire to alarm device as per detailed wiring diagram from our website. If
no alarm is required, isolate orange wire with a wirenut.
Some evaporators provide numbered terminals for connection of the gray and purple overflow alarm
wires directly into the PCB, refer to relevant factory approved diagrams for correct wiring instructions.
Most VRF systems e.g. City Multi, ECO-I, VRF III and Multi-V require constant communication between
all evaporators in the system so the communication wire cannot be used as part of the overflow alarm,
refer to relevant factory approved diagrams for correct wiring instructions.
NOTE: CONNECTION OF THE HIGH LEVEL/OVERFLOW SWITCH IS MANDATORY AND FAILURE TO
DO SO WILL INVALIDATE PUMP WARRANTY!
11
Wiring / Cableado
ES
ENG
CONFIRME QUE LA FUENTE DE ALIMENTACIÓN PRINCIPAL ESTÈ AISLADA. Coloque el cable de
alimentación por el evaporador de modo que llegue a las terminales entrantes de alimentación. Conecte
los cables de energia y de la alarma de sobrenivel segun el diagrama pertinente y adhiera la etiqueta de
advertencia en la parte delantera de la cubierta del terminales.
NO USE LINEAS INDEPENDIENTES DE 115 o 230 VOLTIOS PARA ALIMENTAR LA BOMBA, YA QUE ESTAS
NO SON A PRUEBA DE FALLAS Y SE PUEDE CAUSAR DERRAMES DEL CONDENSADO.
CABLEADO 1. Comprobar que el voltaje de la bomba coincida con el del evaporador y que el voltaje
real suministrado sea suficiente para accionar la bomba. 2. Coloque el cable de alimentación de
la bomba a las terminales entrantes en el evaporador de modo que la bomba cuente con energia
permanentemente, sin importar la operación del evaporador. 3. Conecte el fusible en línea (1 amperio)
suministrado en uno de los cables de alimentación de entrada a la bomba. 4. Conecte la alarma de alto
nivel/derrame, quitando el cable de comunicación del condensador desde su terminal en el evaporador y
conectandolo al cable gris proveniente de la bomba con una tuerca de cable (o una conector engarzado
donde ello sea obligatorio).
5. Conecte el cable morado al terminal de comunicación en el evaporador. Esto evitara que la unidad
opere en caso de bloqueo o fallas en la bomba. Observe que este circuito pueda soportar un máximo
de 5 amperios. Si se requiere de una alarma externa, conecte el cable naranja (N/O) a la alarma segun
el diagrama que se detalla en nuestro sitio web. Si no se requiere de la alarma, se debera aislar el cable
naranja con una tuerca de cable.
Algunos evaporadores cuentan con las terminales marcadas o numeradas, para la conexión directa en
la (tablilla de circuito impreso) PCB, de los cables morado y gris de la alarma de sobre nivel, consulte los
diagramas aprobados de fábrica para las correctas instrucciónes de alambrado y/o conexionado.
La mayoría de los sistemas VRF (Flujo Variable de Refrigerante) como City Multi, ECO-I, VRF III and
Multi-V requieren de una comunicación constante entre todos los evaporadores del sistema por lo que
el cable de comunicación no puede ser usado como parte de la alarma de sobre nivel , consulte los
diagramas aprobados de fábrica para las correctas instrucciones de alambrado y/o conexionado.
NOTA: LA CONEXION DEL INTERRUPTOR POR ALTO NIVEL/DERRAME ES FUNDAMENTAL Y SI NO SE
REALIZA, SE INVALIDARA LA GARANTIA DE LA BOMBA!
N
NL 3G
neutral neutro
terminal block in condenser
bloque de terminales
en condensador
1 amp fuse
1 amp fusible
wire nut
or crimp
tuerca o
engarce
wire nut
or crimp
tuerca o
engarce
terminal block in
evaporator
bloque de terminales
en evaporador
incoming 115V AV
power terminals
permanently live
entrantes de 115V CA
permanentemente activos
pump bomba
ground tierra
green verde
white blanco
black negro
gray common gris común
3 amps max 3 amp. máx.
gray common gris común
3 amps max 3 amp. máx.
live activo
white blanco
black negro
ground tierra
ground tierra
3 amps max 3 amp. máx.
3 amps max 3 amp. máx.
purple (N/C) morado (norm. cerr.)
communication wire
cable de comunicación
cable de comunicación
L
3
G
L1
L
1 L2 G
line 1 línea 1
terminal block in condenser
bloque de terminales
en condensador
1 amp fuse
1 amp fusible
terminal block
in evaporator
bloque de terminales
en evaporador
incoming 208/230V AC
power terminals
permanently live
entrantes de 208/230V CA
terminales de aliment
permanentemente activos
pump bomba
ground tierra
green verde
red rojo
black negro
line 2 línea 2
red rojo
black negro
purple (N/C) morado (norm. cerr.)
communication wire
L2
G
3
3
N
NL 3G
neutral neutro
terminal block in condenser
bloque de terminales
en condensador
1 amp fuse
1 amp fusible
wire nut
or crimp
tuerca o
engarce
wire nut
or crimp
tuerca o
engarce
terminal block in
evaporator
bloque de terminales
en evaporador
incoming 115V AV
power terminals
permanently live
entrantes de 115V CA
permanentemente activos
pump bomba
ground tierra
green verde
white blanco
black negro
gray common gris común
3 amps max 3 amp. máx.
gray common gris común
3 amps max 3 amp. máx.
live activo
white blanco
black negro
3 amps max 3 amp. máx.
3 amps max 3 amp. máx.
purple (N/C) morado (norm. cerr.)
communication wire
cable de comunicación
cable de comunicación
L
3
G
L1
L
1 L2 G
line 1 línea 1
terminal block in condenser
bloque de terminales
en condensador
1 amp fuse
1 amp fusible
terminal block
in evaporator
bloque de terminales
en evaporador
incoming 208/230V AC
power terminals
permanently live
entrantes de 208/230V CA
terminales de aliment
permanentemente activos
pump bomba
ground tierra
green verde
red rojo
black negro
line 2 línea 2
red rojo
black negro
purple (N/C) morado (norm. cerr.)
communication wire
L2
G
3
3
orange wire – do not use, isolate with wire nut
cable naranja – no la use, aislar con una tuerca de cable
orange wire – do not use, isolate with wire nut
cable naranja – no la use, aislar con una tuerca de cable
orange wire – do not use, isolate with wire nut
cable naranja – no la use, aislar con una tuerca de cable
THESE ARE TYPICALLY THE COMMUNICATIONS TERMINALS
COMUNMENTE CORRESPONDEN A LOS TERMINALES DE COMUNICACION
orange wire – do not use, isolate with wire nut
cable naranja – no la use, aislar con una tuerca de cable
MINI ORANGE 115V AC / CA MINI ORANGE 208/230V & UNIVOLT AC / CA
* THESE ARE TYPICALLY THE COMMUNICATIONS TERMINALS IN SINGLE AND MULTIZONE
SYSTEMS.VRF SYSTEMS
ARE WIRED DIFFERENTLY, REFER TO FACTORY APPROVED DIAGRAMS FOR CORRECT WIRING
INSTRUCTIONS.
* TÍPICAMENTE ESTÁS SON TERMINALES DE COMUNICACIÓN EN SISTEMAS DE UNA ZONA Y
MULTI-ZONA. LOS SISTEMAS VRF(FLUJO VARIABLE DE REFRIGERANTE) SON ALAMBRADOS
DE MANERA DIFERENTE, CONSULTE LOS DIAGRAMAS APROBADOS DE FÁBRICA PARA LAS
CORRECTAS INSTRUCCIONES DE ALAMBRADO Y/O CONEXIONADO.
NOTE: NO GROUND IS REQUIRED FOR MAXI ORANGE PUMPS AS THEY ARE CLASS II APPLIANCES
NOTA: LAS BOMBAS MAXI ORANGE NO REQUIEREN PUESTA A TIERRA, YA QUE ESTOS SON APARATOS
DE CLASE II.
ENG
ES
THESE ARE GENERIC DIAGRAMS FOR REFERENCE PURPOSES ONLY AS WIRING PROTOCOLS VARY
FROM ONE MINISPLIT MANUFACTURER TO ANOTHER.
FACTORY APPROVED WIRING DIAGRAMS FOR MOST MODELS OF ALL MAJOR MINISPLIT BRANDS CAN BE FOUND
ON OUR WEBSITE AT www.airtecproducts.com or call 1 800 324-7832 for onsite assistance.
ÉSTOS SON DIAGRAMAS GENÉRICOS SÓLO PARA FINES DE REFERENCIA, YA QUE LOS PROTOCOLOS
DE CABLEADO VARÍAN ENTRE LOS FABRICANTES DE UNIDADES MINISPLIT.
LOS DIAGRAMAS DE CABLEADO APROBADOS POR LA FÁBRICA PARA TODOS LOS PRINCIPALES MODELOS DE MARCAS DE UNIDADES
MINISPLIT SE PUEDEN ENCONTRAR EN NUESTRO SITIO WEB: www.airtecproducts.com o bien puede llamar al 1 800 324-7832 para solicitar
asistencia en terreno.