11. Used Parameters
KSW-81
A.. Inverter
Par. Description Fieldbus-
address
A91.0
Global
r=3, w=3
PZD Setpoint Mapping 2Rx 1. mapped Parameter: If more parameters are to be imaged
than can be specified in A90, this parameter offers a possible extension. See A90.0.
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 16 C0 00 hex
205Bh 0h
A91.1
Global
r=3, w=3
PZD Setpoint Mapping 2Rx 2. mapped Parameter: For extension of A90, see A90.1.
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 16 C0 01 hex
205Bh 1h
A91.2
Global
r=3, w=3
PZD Setpoint Mapping 2Rx 3. mapped Parameter: For extension of A90, See A90.2.
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 16 C0 02 hex
205Bh 2h
A91.3
Global
r=3, w=3
PZD Setpoint Mapping 2Rx 4. mapped Parameter: For extension of A90, see A90.3.
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 16 C0 03 hex
205Bh 3h
A91.4
Global
r=3, w=3
PZD Setpoint Mapping 2Rx 5. mapped Parameter: For extension of A90, see A90.4.
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 16 C0 04 hex
205Bh 4h
A91.5
Global
r=3, w=3
PZD Setpoint Mapping 2Rx 6. mapped Parameter: For extension of A90, see A90.5.
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 16 C0 05 hex
205Bh 5h
A93
Global
read (1)
PZD Setpoint Len: Indicator parameter which indicates the length in bytes of the expected
process data with reference values (data from PROFIBUS master to inverter) for the current
parameterization.
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 17 40 00 hex
1 Only visible when a PROFIBUS device controller is selected in the device configuration or the
appropriate blocks were used with the option for free, graphic programming.
205Dh 0h
A94.0
Global
r=1, w=1
PZD ActValue Mapping Tx 1. mapped Parameter: Address of the parameter which is
imaged first in the contents of the process data channel (sending direction as seen by the inverter).
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 17 80 00 hex
205Eh 0h
A94.1
Global
r=1, w=1
PZD ActValue Mapping Tx 2. mapped Parameter: Address of the parameter which is
imaged second in the contents of the process data channel (sending direction as seen by the
inverter).
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 17 80 01 hex
205Eh 1h
A94.2
Global
r=1, w=1
PZD ActValue Mapping Tx 3. mapped Parameter: Address of the parameter which is
imaged third in the contents of the process data channel (sending direction as seen by the inverter).
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 17 80 02 hex
205Eh 2h
A94.3
Global
r=1, w=1
PZD ActValue Mapping Tx 4. mapped Parameter: Address of the parameter which is
imaged fourth in the contents of the process data channel (sending direction as seen by the
inverter).
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 17 80 03 hex
205Eh 3h
A94.4
Global
r=1, w=1
PZD ActValue Mapping Tx 5. mapped Parameter: Address of the parameter which is
imaged fifth in the contents of the process data channel (sending direction as seen by the inverter).
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 01 17 80 04 hex
205Eh 4h