Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-77
A.. Inverter
Par. Description Fieldbus-
address
A63
Global, OFF
r=1, w=1
Axis selector 0 source: There are 2 "axis selector 0/1" signals with which one of the max. of 4
axes are selected in binary coding. The A63 parameter specifies where bit 0 for the axis selection is
coming from. The possible selections "0:Low" and "1:High" are the same as fixed values. With
A63=0:Low, the bit is set permanently to 0. With A63=1:High, it is permanently set to 1. With
A63=3:BE1 ... 28:BE13-inverted, the axis selection can be made via the selected binary input. With
A63=2:Parameter, A180, bit 3 is used as the signal source (global parameter).
NOTE
- Axis switchover only possible with "enable off"
- With the FDS 5000, the axes can only be used as parameter records for a motor. The
POSISwitch
®
AX 5000 option cannot be connected.
0: Low;
1: High;
2: parameter;
3: BE1;
4: BE1-inverted;
5: BE2;
6: BE2-inverted;
7: BE3;
8: BE3-inverted;
9: BE4;
10: BE4-inverted;
11: BE5;
12: BE5-inverted;
13: BE6;
14: BE6-inverted;
15: BE7;
16: BE7-inverted;
17: BE8;
18: BE8-inverted;
19: BE9;
20: BE9-inverted;
21: BE10;
22: BE10-inverted;
23: BE11;
24: BE11-inverted;
25: BE12;
26: BE12-inverted;
27: BE13;
28: BE13-inverted;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 0F C0 00 hex
203Fh 0h
A64
Global, OFF
r=1, w=1
Axis selector 1 source: There are 2 "axis selector 0/1" signals with which one of the max. of 4
axes are selected in binary coding. The A64 parameter specifies where bit 0 for the axis selection is
coming from. The possible selections "0:Low" and "1:High" are the same as fixed values. With
A64=0:Low, the bit is set permanently to 0. With A64=1:High, it is permanently set to 1. With
A64=3:BE1 ... 28:BE13-inverted, the axis selection can be made via the selected binary input. With
A64=2:Parameter, A180, bit 4 is used as the signal source (global parameter).
NOTE
- Axis switchover only possible with "enable off"
- With the FDS 5000, the axes can only be used as parameter records for a motor. The
POSISwitch
®
AX 5000 option cannot be connected.
0: Low;
1: High;
2: parameter;
3: BE1;
4: BE1-inverted;
5: BE2;
6: BE2-inverted;
7: BE3;
8: BE3-inverted;
2040h 0h