Specifications
Table Of Contents
- Cover Sheet
- Table of Contents
- Notes on Safety
- Introduction
- Selecting the Type of Reference Value
- Representing the Reference Values in User Units
- Combining the Reference Values
- Available Reference Values
- Additional Functions
- Parameterizing the Speed and Torque Limits
- Additional Functions
- Fieldbus
- Used Parameters
- Global Presence
- Publication
- STÖBER Homepage
- STÖBER Product Range

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-72
A.. Inverter
Par. Description Fieldbus-
address
A10.4
Global
r=0, w=0
Userlevel: Specifies the access level of the user for the parameters via the "system bus"
communication path. Each parameter has one level each for read or write accesses. A parameter
can only be read or changed with the necessary access level.
The higher the set level the more parameters can be accessed.
Possible settings:
0: Monitor; The elementary indicators can be monitored. General parameters can be changed.
1: Standard; The primary parameters of the selected application can be monitored and changed.
2: Extended; All parameters for commissioning and optimization of the selected application can be
monitored and changed.
3: Service; Service parameters. Permit a comprehensive diagnosis.
Value range: -32768 ... 3 ... 32767
Fieldbus: 1LSB=1; Type: I16; USS-Adr: 01 02 80 04 hex
200Ah
Array
4h
A11.0
Global
r=1, w=1
Edited Axe: Specifies the axis to be edited via device display. Axis to be edited (A11) and active
axis (operating indicator, E84) must not be identical (e.g., axis 1 can be edited while the inverter
continues with axis 2).
Value range: 0 ... 0: axis 1 ... 3
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 02 C0 00 hex
200Bh
Array
0h
A11.1
Global
r=1, w=1
Edited Axe: Selects the axis to be parameterized which is addressed with CANopen with SDO
channel 1 or with PROFIBUS DP-V0. The axis to be edited (A11) and the active axis (operation
indicator, E84) must not be identical (e.g., axis 1 can be edited while the inverter continues with
axis 2). With PROFIBUS DP-V0, a distinction can be made between two axes with the PKW
service. Axis 1 or axis 2 is selected with A11.1=0. Axis 3 or axis 4 is selected with A11.1=1.
Value range: 0 ... 0: axis 1 ... 3
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 02 C0 01 hex
200Bh
Array
1h
A11.2
Global
r=1, w=1
Edited Axe: Selects the axis to be parameterized which is addressed with CANopen with SDO
channel 2. The axis to be edited (A11) and the active axis (operation indicator, E84) must not be
identical (e.g., axis 1 can be edited while the inverter continues with axis 2).
Value range: 0 ... 0: axis 1 ... 3
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 02 C0 02 hex
200Bh
Array
2h
A11.3
Global
r=1, w=1
Edited Axe: Selects the axis to be parameterized which is addressed with CANopen with SDO
channel 3. The axis to be edited (A11) and the active axis (operation indicator, E84) must not be
identical (e.g., axis 1 can be edited while the inverter continues with axis 2).
Value range: 0 ... 0: axis 1 ... 3
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 02 C0 03 hex
200Bh
Array
3h
A11.4
Global
r=1, w=1
Edited Axe: Selects the axis to be parameterized which is addressed with CANopen with SDO
channel 4. The axis to be edited (A11) and the active axis (operation indicator, E84) must not be
identical (e.g., axis 1 can be edited while the inverter continues with axis 2).
Value range: 0 ... 0: axis 1 ... 3
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 02 C0 04 hex
200Bh
Array
4h
A12
Global
r=1, w=1
Language: Language on the display.
0: German/primary language;
1: English/secondary language;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 03 00 00 hex
200Ch 0h
A21
Global, OFF
r=1, w=2
Brake resistor R: Resistance value of the brake resistor being used.
Value range in Ohm: 200.0 ... 300,0 ... 600.0
Fieldbus: 1LSB=0,1Ohm; Type: I16; USS-Adr: 01 05 40 00 hex
2015h 0h