11. Used Parameters
KSW-70
11 USED PARAMETERS
11.1 Parameter legend
Par. Description Fieldbus
address
C230
Global
r=2, w=2
Torque limit: Specification for the torque limit (absolute value) via fieldbus if the signal source is
C130=4:Parameter.
Value range in %: -200 to 200 to 200
Fieldbus: 1LSB=1·%; PDO ; type: I16; (raw value:32767 = 200 %); USS address: 03 39 80 00 hex
24E6h 0h
11.2 Parameter list
A.. Inverter
Par. Description Fieldbus-
address
A00.0
Global
r=0, w=0
Save values & start: When this parameter is activated, the inverter saves the current
configuration and the parameter values in the Paramodule. After power-off, the inverter starts with
the saved configuration. If the configuration data on the inverter and Paramodul are identical, only
the parameters are saved (speeds up the procedure).
NOTE
Do not turn off the power of the control section (device version /L:24 V, device version /H: supply
voltage) while the action is being executed. If the power is turned off while the action is running this
causes incomplete storage. After the device starts up again the fault "*ConfigStartERROR
parameters lost" appears on the display. Only several 1000 storage procedures are possible per
Paramodul. When this limit has almost been reached, result 14 is indicated after the storage
procedure. When this happens, replace Paramodul as soon as possible.
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 00 00 00 hex
2000h 0h
A00.1
Global
read (0)
Process: Shows the progress of the "save vales" action in %.
Fieldbus: 1LSB=1%; Type: U8; USS-Adr: 01 00 00 01 hex
2000h 1h
A00.2
Global
read (0)
Result: Result of the "save values" action
0: error free;
10: write error;
11: invalid data;
12: write error;
14: warning;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 01 00 00 02 hex
2000h 2h
Access level for read (r=2) and
write accesses (w=2)
Fieldbus:
1st position: Scaling for integer (PROFIBUS and CAN bus)
2nd position: - PDO – Parameters can be imaged as process data.
- Blank – Parameter can only be accessed via PKW (PROFIBUS) or SDO
(CAN bus).
3rd position: Data type. See application manual, chapter 3.2.
4th position: Scaling for raw values
5th
p
osition: USS address
Global – Parameter is not dependent on
axis.
Achse – Parameter is axis-specific.
Off – Parameter can only be changed
when enable is off.
V
alue range:
Specification of unit, minimum
and maximum value
The default setting is
underlined.
PROFIBUS = PNU (PKW1)
CAN-Bus = Index
PROFIBUS = Subindex
CAN-Bus = Subindex