Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
9. Additional Functions
KSW-66
How to scale I32 values to I16
format …
Parameters D98.X and D99.X can be used to scale I32 parameters, which are shown in
user units, to I16 values in relation to D56. Go to page 11 of the Assistant and proceed
as described below (Figure 9-6):
Enter the I32 parameter in D98.X.
The value scaled in I16 can be read out in the same element in array D99.X. This
value can then be entered in the "range control" function.
Scaling can also be used to indicate I32 values on analog outputs.
Figure 9-6 Parameterizing the scaling
Status signals
Signal Function
Fieldbus
Image
Single
Parameter
Range control 1,
red, below
The signal is 1:active when the value indicated in D69 is below the limit
entered in D64 (D69 < D64).
D202 Bit0 D190
Range control 1,
yellow, below
The signal is 1:active when the value indicated in D69 is between the values
D64 and D65 (D64 < D69 < D65).
D202 Bit1 D191
Range control 1,
green
The signal is 1:active when the value indicated in D69 is between the values
D65 and D66 (D65 < D69 < D66).
D202 Bit2 D192
Range control 1,
yellow, above
The signal is 1:active when the value indicated in D69 is between the values
D66 and D67 (D66 < D69 < D67).
D202 Bit3 D193
Range control 1,
red, above
The signal is 1:active when the value indicated in D69 is above the limit
entered in D67 (D69 > D67).
D202 Bit4 D194
Range control 2,
red, below
The signal is 1:active when the value indicated in D79 is below the limit
entered in D74 (D79 < D74).
D202 Bit5 D195
Range control 2,
yellow, below
The signal is 1:active when the value indicated in D79 is between the values
D74 and D75 (D74 < D79 < D75).
D202 Bit6 D196
Range control 2,
green
The signal is 1:active when the value indicated in D79 is between the values
D75 and D76 (D75 < D79 < D76).
D202 Bit7 D197
Range control 2,
yellow, above
The signal is 1:active when the value indicated in D79 is between the values
D76 and D77 (D76 < D79 < D77).
D202 Bit8 D198
Range control 2,
red, above
The signal is 1:active when the value indicated in D79 is above the limit
entered in D77 (D79 > D77).
D202 Bit9 D199