9. Additional Functions
KSW-65
How to parameterize
the events …
Go to page 10.3 of the Assistant (Figure 9-55) to parameterize the events. The level of
the events is set in U100 or U110 for range control 1 and in U120 or U130 for range
control 2. You can select from the following settings.
• When 0:inactive is set an exceeded limit has no reaction.
• With all other settings a parameter is indicated in which you can enter a designation.
This designation is shown on the inverter's display when the event is triggered.
• When 1:message is parameterized the choosen designation is shown on the display.
Operation is continued.
• When 2:warning is set a parameter is indicated in which you enter a time. When the
event occurs operation is continued for this time. The event is indicated on the display.
After this time expires the warning is converted into a fault. The inverter switches to the
device state "fault."
• When you parameterize 3:fault the inverter changes immediately to the device state
"fault" when a limit is violated.
Figure 9-5 Parameterizing the events for range control