Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
7. Additional Functions
KSW-52
Status signals
Signal Function
Fieldbus
Image
Single
Parameter
Direction
Indication of the "direction" signal regardless of the source set in D100. D201 Bit0 D300
Active direction
The signal shows the direction at the end of the reference value path. A low
level means a positive reference value. A high level means a negative
reference value. The parameter D57 does not affect this signal.
D201 Bit1 D430
Jog active
The signal is 1:active when all the following conditions are fulfilled:
- The jog enable (selector D105) or the jog reference value enable (D55 and
D113 additional enable 2) is active.
- A stop command (selector D102) is queued.
- The speed has reached the range -C40 to +C40 once.
D201 Bit8 D437
Stop active
When the level is high a stop command is queued (D302) and the actual
motor speed has reached the range -C40 to +C40 once.
D201 Bit9 D438
Limit switch
When the level is high one of the limit switches has triggered (D303 or D304). D202 Bit13 D462
Warning
When the level is high a warning was determined (E81 = 2). D202 Bit14 D463
Switch-on disable
When the level is high the inverter is in the state "switch-on disable" (E48 = 1). D202 Bit15 D464