6. Available Reference Values
KSW-38
Binary input signals
Signal Function Selector
Fieldbus
Image
Display
Parameter
Time ON Time OFF
Motorized pot up
source
A high level increases the motor
potentiometer reference value in steps
or continuously, depending on D43.
D114 D211 Bit0 D314 - -
Motorized pot
down source
A high level decreases the motor
potentiometer reference value in steps
or continuously, depending on D43.
D115 D211 Bit1 D315 - -
Motorized pot
preset source
A high level sets the current motor
potentiometer reference value to the
value entered in D44.
D116 D211 Bit2 D316 D416.0 D416.1
Motorized pot
ramp selection
When D40 bit 7 is active the signal
motorized pot ramp source can be used
to switch between D41 and D42. D41 is
used for low level. The ramp D42 is used
for high level.
D117 D211 Bit3 D317 D417.0 D417.1
Status signals
Signal Function
Fieldbus
Image
Single
Parameter
Motorized pot out
constant
Signal indication depends on D43.
When the value 0 is entered in D43 the motor potentiometer (MOP) reference
value is changed continuously. Signal 1 is active when the signals MOP up
and MOP down are simultaneously inactive or simultaneously active.
When D43 is a value other than 0, reference values are changed in steps. The
signal is 1:active when a step is completed and becomes 0:inactive when a
new step is started.
D200 Bit13 D187
Motorized pot limit
reached
A high level means that the motor potentiometer reference value has reached
the value in D45 or D46.
D200 Bit14 D188