6. Available Reference Values
KSW-32
How to parameterize the
selection of the preset values …
To parameterize the selection of the preset values, proceed as shown below
(Figure 6-10):
• Set the sources of your switchover signals (e.g., BE5 and BE6) in D125.0 and D125.1.
With fieldbus select the setting 2: parameter. In fieldbus mode bits 3 to 5 of the control
word D212 are used as sources.
• Set the enable of the switchover in D128 or D129. The use of an enable prevents
undesired states from occurring. The enable can be given with a positive edge (D128)
or a high level (D129). If the switchover is to take effect immediately, set D129 =
1:high.
• Check the selection in D325 during online operation of POSITool.
Figure 6-10 Parameterizing the preset value selectors
NOTE
Remember that the signals set in D128 and D129 also enable the switchover of the
preset reference values. For more information, see chapter 6.2.2.
How to define preset values …
Preset values are entered in the middle section of page 3.4.4 as described below
(Figure 6-11):
• Use the up/down arrow keys to select the preset value which you want to enter.
• Enter the designation of the preset value (fix value name) (e.g., feed) in the parameter
D26.x.
• Enter the value of the preset value (fix value) (e.g., 100 [rpm]) in D27.x.
• Select the next preset value and keep repeating the procedure until you have defined
all necessary preset values.
Figure 6-11 Entering preset value 0
How to monitor preset values …
After you have transferred your parameterization at the end and an active online
connection has been established between POSITool and the inverter, you can check
your settings in the bottom half of the screen.
Figure 6-12 Monitoring a preset value