Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
6. Available Reference Values
KSW-31
Signal Function Selector
Fieldbus
Image
Display
Parameter
Time ON Time OFF
Enable preset reference
value / preset value
(edge)
D128
D212
Bit14
D328 D428.0 D428.1
Enable preset reference
value / preset value (level)
After a switchover of the preset
reference values, preset values, and
accelerating and decelerating ramps,
the change must be accepted with an
enable signal. This prevents
undesired states. The enable is given
when there is a positive edge with the
signal enable preset reference
value/preset value (edge) or a HIGH
level with the signal enable preset
reference value/preset value (level).
D129
D212
Bit15
D329 D429.0 D429.1
1
D212 bit 3 has a double allocation. When both preset reference values and preset values are addressed via fieldbus, this bit is evaluated as
preset value select 0. This means that eight preset reference values and eight preset values can be selected at the same time. If no preset
values are addressed via fieldbus (i.e., they are addressed via terminals or are not used at all), D212 bit 3 is evaluated as preset reference
value select 3 and 16 preset reference values can be addressed.
6.2.2 Preset Values
Preset values
The preset values are parameterized on page 3.4.4 of the Assistant (Figure 6-9). The
upper part of this page contains the parameterization of the preset value selection. The
middle section covers the entry of the preset values, and the bottom part concerns the
display parameters for monitoring the current preset value.
Figure 6-9 Parameterizing the preset values