6. Available Reference Values
KSW-27
How to enter preset reference
values …
Preset reference values are entered on page 3.4.1 (Figure 6-4). Proceed as follows:
• Use the up/down arrow keys to select the preset reference value which you want to
enter.
• Enter the designation of the preset reference value (e.g., feed) in parameter D10.x.
• Enter the value of the preset value (e.g., 100 [rpm] in D11.x.
• Select the next preset reference value and keep repeating the procedure until you
have defined all necessary preset reference values.
Figure 6-4 Setting a preset reference value
How to parameterize the
selection of the preset reference
values …
To parameterize the preset value selection proceed as shown below (Figure 6-5):
• Go to page 3.4.2 of the Assistant.
• Set the sources of your switchover signals (e.g., BE1 to BE3) in D124.0 to D124.2.
Select the setting 2: parameter for fieldbus mode. Bits 0 to 3 of control word D212 are
used as sources for fieldbus mode.
• Set the enable of the switchover in D128 or D129. The enable is necessary to prevent
any undesired states from occurring during the switchover. You can activate the
enable with a positive edge (D128) or a high level (D129). If the switchover is to take
effect immediately set D129 = 1:High.
Figure 6-5 Parameterization of the preset reference value selectors