Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-246
Z.. Fault counter
Par. Description Fieldbus-
address
Z70
Global
read (3)
Parameter consistency: The parameter indicates how frequently event 70:Parameter
consistency has occurred.
Event description:
Trigger: The parameterization is contradictory.
Cause: 1: no servoencoder; no servo-type encoder; control mode B20 is set to "servo"
but no appropriate encoder is selected (B26, H.. parameter).
2: X120 direction; X120 is used as source in one parameter but is
parameterized in H120 as drain (or vice versa).
3: B12<->B20; Control mode B20 is not set to servo but the nominal motor
current (B12) exceeds the 4-kHz nominal current (R24) of the device by more
than 1.5 times.
4: B10<->H31; Resolver/motorpoleno.; the set motor pole number (B10) and the
resolver pole number (H31) do not match.
5: neg.slip; with the control modes V/f, SLVC or VC (B20). The values for motor
nominal speed (B13), motor nominal frequency (B15) and motor pole number
(B10) indicate a negative slip.
7: B26:SSI-Slave; SSI slave may not be used as motor encoder
(synchronization problems).
8: C01>B83; C01 may not be greater than B83.
Level: Fault
Acknowledgment: Turn device off/on or programmed acknowledgment.
Other: With an incorrect parameterization, a fault is not triggered until enabling takes
place.
Fieldbus: 1LSB=1; Type: U16; USS-Adr: 1A 11 80 00 hex
5246h 0h