Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-245
Z.. Fault counter
Par. Description Fieldbus-
address
Z65
Global
read (3)
Application event 5: The parameter indicates how frequently event 65:Application event 5 has
occurred.
Event description:
Trigger: Application specific or by free programming option.
Cause: Can be programmed as desired for each axis separately.
Level: Can be parameterized in system parameters U150.
Acknowledgment: Turn device off/on or programmed acknowledgment.
Other: - Message/warning: Evaluation in 256-msec cycle.
- Fault: Evaluation in parameterizable cycle time (A150). Texts, times and level
can be set in parameter group U.. starting with U100.
Fieldbus: 1LSB=1; Type: U16; USS-Adr: 1A 10 40 00 hex
5241h 0h
Z66
Global
read (3)
Application event 6: The parameter indicates how frequently event 66:Application event 6 has
occurred.
Event description:
Trigger: Application specific or by free programming option.
Cause: Can be programmed as desired for each axis separately.
Level: Can be parameterized in system parameters U160.
Acknowledgment: Turn device off/on or programmed acknowledgment.
Other: - Message/warning: Evaluation in 256-msec cycle.
- Fault: Evaluation in parameterizable cycle time (A150). Texts, times and level
can be set in parameter group U.. starting with U100.
Fieldbus: 1LSB=1; Type: U16; USS-Adr: 1A 10 80 00 hex
5242h 0h
Z67
Global
read (3)
Application event 7: The parameter indicates how frequently event 67:Application event 7 has
occurred.
Event description:
Trigger: Application specific or by free programming option.
Cause: Can be programmed as desired for each axis separately.
Level: Can be parameterized in system parameters U170.
Acknowledgment: Turn device off/on or programmed acknowledgment.
Other: - Message/warning: Evaluation in 256-msec cycle.
- Fault: Evaluation in parameterizable cycle time (A150). Texts, times and level
can be set in parameter group U.. starting with U100.
Fieldbus: 1LSB=1; Type: U16; USS-Adr: 1A 10 C0 00 hex
5243h 0h
Z68
Global
read (3)
External fault 2: The parameter indicates how frequently event 68:External fault 2 has occurred.
Event description:
Trigger: Application specific or by free programming option.
Level: Fault
Acknowledgment: Turn device off/on or programmed acknowledgment.
Other: Should be used for application events which can only be parameterized at the
"fault" level.
Fieldbus: 1LSB=1; Type: U16; USS-Adr: 1A 11 00 00 hex
5244h 0h
Z69
Global
read (3)
Motor connection: The parameter indicates how frequently event 69:Motor connection has
occurred.
Event description:
Trigger: Connection error of the motor.
Cause: 1: MotorNotDiscon; the contactor did not open
when the axis changed. This
cause can only be determined when at least two phase contacts are stuck and
the DC link is charged (see E03). No magnetization could be established with
asynchronous motors.
2: No motor; possibly no motor connected or line to motor interrupted.
Level: Can be parameterized as inactive or warning in U12.
Acknowledgment: Turn device off/on or programmed acknowledgment.
Fieldbus: 1LSB=1; Type: U16; USS-Adr: 1A 11 40 00 hex
5245h 0h