Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-235
U.. Protection functions
Par. Description Fieldbus-
address
U20
Axis
r=3, w=3
Level M-Max limit: When the calculated motor torque exceeds the current torque limit in E62
during stationary operation, U20 is triggered.
0: inactive; Device does not react to the triggering of U20.
1: Message
; Triggering of U20 is only indicated. The device continues to remain ready for
operation.
2: Warning; After expiration of the tolerance time in U21, the device assumes fault status.
3: Fault; The device immediately assumes fault status after U20 is triggered.
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 15 05 00 00 hex
4814h 0h
U21
Axis
r=3, w=3
Time M-Max limit: Can only be set when U20=2:Warning. Defines the time during which a drive
overload is tolerated. After expiration of this time, the device assumes fault status.
Value range in s: 1.00 ... 10,00 ... 60.00
Fieldbus: 1LSB=0,01s; Type: U8; (raw value:2 Bit=1·s); USS-Adr: 15 05 40 00 hex
1 Only when the appropriate event level is parameterized to 2:Warning.
4815h 0h
U80
Axis
r=3, w=3
Fault sample parameter 0: Each of the 10 fault memory entries has space for user-defined
data which are also saved when a fault is triggered. The parameter to be recorded is set here.
Value range: A00 ... E91 ... A.Gxxx.yyyy (Parameter number in plain text)
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 15 14 00 00 hex
4850h 0h
U81
Axis
r=3, w=3
Fault sample parameter 1: Each of the 10 fault memory entries has space for user-defined
data which are also saved when a fault is triggered. The parameter to be recorded is set here.
Value range: A00 ... E00 ... A.Gxxx.yyyy (Parameter number in plain text)
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 15 14 40 00 hex
4851h 0h
U82
Axis
r=3, w=3
Fault sample parameter 2: Each of the 10 fault memory entries has space for user-defined
data which are also saved when a fault is triggered. The parameter to be recorded is set here.
Value range: A00 ... E90 ... A.Gxxx.yyyy (Parameter number in plain text)
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 15 14 80 00 hex
4852h 0h
U83
Axis
r=3, w=3
Fault sample parameter 3: Each of the 10 fault memory entries has space for user-defined
data which are also saved when a fault is triggered. The parameter to be recorded is set here.
Value range: A00 ... E191 ... A.Gxxx.yyyy (Parameter number in plain text)
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 15 14 C0 00 hex
4853h 0h
U100
Axis
r=3, w=3
Level application event 0: Application-specific event no. 60. Starting with the level
"1:Message," the display shows the event number with the text specified in U102 (e.g., "60:My
fault") when this event occurs.
0: inactive;
1: Message;
2: Warning;
3: Fault;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 15 19 00 00 hex
4864h 0h
U101
Axis
r=3, w=3
Time application event 0: Can only be set with U100=2:Warning. Defines the time during
which the event remains a warning. After expiration of this time, the device assumes fault status.
Value range in s: 0.00 ... 0,00 ... 63.75
Fieldbus: 1LSB=0,01s; Type: U8; (raw value:2 Bit=1·s); USS-Adr: 15 19 40 00 hex
1 Only when the appropriate event level is parameterized to 2:Warning.
4865h 0h
U102
Axis
r=3, w=3
Text application event 0: Text which appears on the display when the event is triggered.
Default setting: Range 1 lowerLim
Fieldbus: Type: Str16; USS-Adr: 15 19 80 00 hex
4866h 0h