11. Used Parameters
KSW-225
G.. Technology
Par. Description Fieldbus-
address
G185
Axis
read (2)
PID set value: Display parameter for the PID controller output after the weighting ratio (G16).
Fieldbus: 1LSB=0,1%; PDO ; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 07 2E 40 00 hex
2CB9h 0h
G232
Global
r=2, w=3
Technology reference value: Technology reference value of the "technology controller"
application (control variable of the control loop). The value is processed when G132 is
"4:parameter."
Value range in %: -200.0 ... 0,0 ... 200.0
Fieldbus: 1LSB=0,1%; PDO ; Type: I16; (raw value:32767·LSB=200,0%); USS-Adr: 07 3A 00 00 hex
2CE8h 0h
G233
Global
r=2, w=3
Actual technology value: Technology actual value of the "technology controller" application.
The value is processed when G133 is 4: parameter. The actual value is filtered with a PT1 low pass
(G11) before it is processed on the PID controller.
Value range in %: -200.0 ... 0,0 ... 200.0
Fieldbus: 1LSB=0,1%; PDO ; Type: I16; (raw value:32767·LSB=200,0%); USS-Adr: 07 3A 40 00 hex
2CE9h 0h
G300
Axis
read (2)
Status negate technology reference value: Display parameter for the current signal state
on the input of the technology controller. G300 shows the state regardless of the source selected in
G100.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 07 4B 00 00 hex
2D2Ch 0h
G301
Axis
read (2)
Status PID controller disable: Display parameter for the current signal state on the input of
the technology controller. G301 shows the state regardless of the source selected in G101.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 07 4B 40 00 hex
2D2Dh 0h
G302
Axis
read (2)
Status PID Mode: Display parameter for the current signal state on the input of the PID
controller. G302 shows the state regardless of the mode selected in G14.
Fieldbus: 1LSB=1; Type: B; USS-Adr: 07 4B 80 00 hex
2D2Eh 0h
G332
Axis
read (2)
Status technology value: Display parameter for the current reference value of the technology
controller after the inversion point.
Fieldbus: 1LSB=0,1%; PDO ; Type: I16; (raw value:32767·LSB=200,0%); USS-Adr: 07 53 00 00 hex
2D4Ch 0h
G333
Axis
read (2)
Status actual technology value: Display parameter for the current actual value of the
technology controller after the low pass filter.
Fieldbus: 1LSB=0,1%; PDO ; Type: I16; (raw value:32767·LSB=200,0%); USS-Adr: 07 53 40 00 hex
2D4Dh 0h