Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-221
G.. Technology
Par. Description Fieldbus-
address
G16
Axis
r=2, w=3
PID ratio: Weighting ratio of the PID controller. When G16 = 0, the PID controller is deactivated.
Value range in %: 0 ... 100 ... 400
Fieldbus: 1LSB=1%; Type: I16; (raw value:32767·LSB=800%); USS-Adr: 07 04 00 00 hex
2C10h 0h
G18
Axis
read (2)
PID P-Part: Observation parameter for monitoring the P portion of the PID controller.
Fieldbus: 1LSB=0,1%; Type: I32; (raw value:16384·LSB=100%); USS-Adr: 07 04 80 00 hex
2C12h 0h
G19
Axis
read (2)
PID I-Part: Observation parameter for monitoring the I portion of the PID controller.
Fieldbus: 1LSB=0,1%; Type: I32; (raw value:16384·LSB=100%); USS-Adr: 07 04 C0 00 hex
2C13h 0h
G90
Global
r=3, w=3
PLL: Activates PLL control.
PLL control synchronizes the inverter with the SYNC telegrams of the CAN bus or the SYNC signal
of the EtherCAT bus.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 07 16 80 00 hex
2C5Ah 0h
G91
Global
r=3, w=3
PLL phase-offset: Time offset value between the arrival of the SYNC telegram and the phase
position of the cycle time on the inverter.
Value range in µs: -32768 ... -800 ... 32767
Fieldbus: 1LSB=1µs; Type: I16; USS-Adr: 07 16 C0 00 hex
2C5Bh 0h
G92
Global
r=3, w=3
PLL gain: Proportional gain of PLL control.
The gain must be reduced when the jitter of the SYNC telegrams increases.
Value range in %: 0.0 ... 20,0 ... 100.0
Fieldbus: 1LSB=0,1%; Type: I32; (raw value:2,14748E9·LSB=100%); USS-Adr: 07 17 00 00 hex
2C5Ch 0h
G93
Global
r=3, w=3
PLL low pass: Determines the limit frequency of the low pass filter of PLL control.
The time must be increased when the jitter of the SYNC telegrams increases.
Value range in ms: 0.0 ... 40,0 ... 200.1
Fieldbus: 1LSB=0,1ms; Type: I32; raw value:1LSB=Fnct.no.11; USS-Adr: 07 17 40 00 hex
2C5Dh 0h
G95
Global
read (3)
PLL status: Shows the status of PLL control.
Bit-0: PLL status
Bit-1: PLL status
00 PLL engaged
01 Engaged, but more than half the control range is utilized (frequency too high).
10 Engaged, but more than half the control range is utilized (frequency too low).
11 PLL not engaged.
Bit-2: Is 1 when PLL has extended the internal cycle time (A150).
Bit-3: Is 1 when control hits the limits of the control range.
Bit-4: Is 1 when the measured cycle time (G96) is greater than the specification (G98).
Bit-5: Is 1 when G90 = inactive (PLL is deactivated).
Bit-6: Reserved
Bit-7: Reserved
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 07 17 C0 00 hex
2C5Fh 0h
G96
Global
read (3)
PLL measured cycle-time: Cycle time of the SYNC telegrams determined by PLL control.
Fieldbus: 1LSB=1µs; Type: I32; USS-Adr: 07 18 00 00 hex
2C60h 0h