Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-217
F.. Control Interface
Par. Description Fieldbus-
address
F83
Axis
r=2, w=2
BA2 on delay: A signal which is output on BA2 can be delayed with the parameters F83 and
F84. When a value is entered in F83, the switchon procedure of the signal is delayed by this
number of milliseconds.
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 06 14 C0 00 hex
1 Only when a board is installed in the bottom option slot.
2A53h 0h
F84
Axis
r=2, w=2
BA2 off delay: A signal which is output on BA2 can be delayed with the parameters F83 and
F84. When a value is entered in F84, the switchon procedure of the signal is delayed by this
number of milliseconds.
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 06 15 00 00 hex
1 Only when a board is installed in the bottom option slot.
2A54h 0h
F85
Axis
r=2, w=2
BA2 inverting: When the parameter F85 is activated, the output of the signal entered in F62 is
inverted on BA2.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 06 15 40 00 hex
1 Only when a board is installed in the bottom option slot.
2A55h 0h
F90
Global
r=2, w=3
Release time axis-switch: Specifies the release time of the contactor used for the axis
switchover. This minimum time is waited before the inverter lets the next contactor be applied.
Value range in ms: 0 ... 20 ... 32767
Fieldbus: 1LSB=1ms; Type: I16; USS-Adr: 06 16 80 00 hex
2A5Ah 0h
F91
Global
r=2, w=3
Set time axis-switch: Specifies the set time of the contactor used for the axis switchover. This
time is at least waited before the inverter lets the axis be electrified.
Value range in ms: 0 ... 20 ... 32767
Fieldbus: 1LSB=1ms; Type: I16; USS-Adr: 06 16 C0 00 hex
2A5Bh 0h
F100
Global, OFF
r=1, w=1
Brake release source: Selection of the source for the "release brake" signal. The signal can be
permanently pre-specified as supplied by the binary inputs or the fieldbus. With F100=2:Parameter,
A180, bit 6 (global parameter) is used as the signal source. This is the setting for fieldbus
operation.
Caution: The "release brake" signal releases the brake regardless of the device state - this may
cause accidental movements.
0: Low;
1: High;
2: parameter;
3: BE1;
4: BE1-inverted;
5: BE2;
6: BE2-inverted;
7: BE3;
8: BE3-inverted;
9: BE4;
10: BE4-inverted;
11: BE5;
12: BE5-inverted;
13: BE6;
14: BE6-inverted;
15: BE7;
16: BE7-inverted;
17: BE8;
2A64h 0h