Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-213
F.. Control Interface
Par. Description Fieldbus-
address
F14
Axis, OFF
r=2, w=2
AE1-mode selector: The reference value mode for AE1 is set in F14. When 0: -10V to 10V is
selected, a voltage reference value can be connected to AE1 in the specified range.
The selections 1 and 2 can be set when a current reference value is specified. With 1: 0 to 20mA
the specification 0 mA is interpreted as the minimum reference value and 20 mA as the maximum
reference value. This interpretation is reversed for the setting 2. In other words, at 0 mA (wire
break) the motor is activated with the maximum reference value (pump control).
Wire break monitoring can be activated in F15 for the settings 3 and 4. With these settings a current
reference value of 4 to 20 mA is connected. With 3: 4 to 20 mA, 4 mA is processed as the minimum
reference value and 20 mA as the maximum reference value. When the selection is 4: 20 to 4 mA,
processing is reversed (i.e., at 4 mA the motor is activated with the maximum reference value).
0: -10V to 10V;
1: 0 to 20mA;
2: 20 to 0mA;
3: 4 to 20mA;
4: 20 to 4mA;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 06 03 80 00 hex
2A0Eh 0h
F15
Axis
r=2, w=2
Wire breakage sensing: When F14 is set to 3: 4 to 20 mA or 4: 20 to 4 mA, wire break
monitoring can be activated in F15. Active wire break monitoring means that application event 4 will
be generated as per the parameterization in U140 to U142 if a wire break occurs. The drive
continues at the velocity which was valid before the wire break until either a fault is generated by
the event parameterization, the enable is switched off or the drive is stopped with a stop or quick
stop command.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 06 03 C0 00 hex
2A0Fh 0h
F21
Axis
r=2, w=2
AE2-Offset: F21 is added to E16. The result is multiplied by F22. This signal is supplied to the
configuration. To compensate for an offset (the value which arrives at the inverter when the
controller specifies 0 V), this must be entered in F21 with the opposite sign.
Value range in V: -10.000 ... 0,000 ... 10.000
Fieldbus: 1LSB=0,001V; Type: I16; (raw value:32767 = 20.000 V); USS-Adr: 06 05 40 00 hex
1 Only when a board is installed in the bottom option slot.
2A15h 0h
F22
Axis
r=2, w=2
AE2-gain: F21 is added to E16. The result is multiplied by F22. This signal is supplied to the
configuration.
Value range in %: -400.0 ... 100,0 ... 400.0
Fieldbus: 1LSB=0,1%; Type: I16; (raw value:32767·LSB=400,0%); USS-Adr: 06 05 80 00 hex
1 Only when a board is installed in the bottom option slot.
2A16h 0h
F23
Axis
r=2, w=2
AE2 ref low pass filter: The time constant for filtering a reference value specified on AE2 is
parameterized in F23.
Value range in ms: 0.0 ... 1,2 ... 200.1
Fieldbus: 1LSB=0,1ms; Type: I32; raw value:1LSB=Fnct.no.11; USS-Adr: 06 05 C0 00 hex
2A17h 0h
F31
Axis
r=2, w=2
AE3-Offset: F31 is added to E74. The result is multiplied by F32. This signal is supplied to the
configuration. To compensate an offset (the value which arrives at the inverter when the controller
specifies 0 V), this must be entered in F31 with opposite sign.
Value range in V: -10.000 ... 0,000 ... 10.000
Fieldbus: 1LSB=0,001V; Type: I16; (raw value:32767 = 20.000 V); USS-Adr: 06 07 C0 00 hex
1 Only when an XEA board is installed in the bottom option slot.
2A1Fh 0h