Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-198
E.. Display Value
Par. Description Fieldbus-
address
E22
Global
read (1)
i2t-device: Level of the thermal device model (i
2
t model). The fault "59:Overtemp.device i2t"
occurs at 105% of full load. When the 100% limit is reached, the inverter triggers the event
"39:Overtemp.device i2t" with the level specified in U02. The output current is limited to the
permissible device nominal current for servo and vector control (B20=2 or 64).
Value range in %: 0 ... 80 ... 255
Fieldbus: 1LSB=1%; PDO ; Type: U8; (raw value:100·LSB=100%); USS-Adr: 05 05 80 00 hex
2816h 0h
E23
Axis
read (1)
i2t-motor: Level of the thermal motor model (i
2
t model). 100% corresponds to full utilization. The
thermal model is based on the design data entered under group B.. (Motor) (i.e., continuous
operation - S1 operation). With more than 100%, the reaction parameterized in U10, U11 is
triggered for the event "45:Overtemp.device i2t."
Value range in %: 0 ... 80 ... 255
Fieldbus: 1LSB=1%; PDO ; Type: U8; (raw value:100·LSB=100%); USS-Adr: 05 05 C0 00 hex
2817h 0h
E24
Global
read (1)
i2t-braking resistor: Level of the thermal braking resistor model (i²t model). 100% corresponds
to full utilization. The data of the braking resistor are specified with A21 ... A23. With more than
100%, the fault "42:TempBrakeRes" occurs.
Value range in %: 0 ... 80 ... 255
Fieldbus: 1LSB=1%; PDO ; Type: U8; (raw value:100·LSB=100%); USS-Adr: 05 06 00 00 hex
2818h 0h
E25
Global
read (1)
Device-temperature: Current device temperature in °C.
Fieldbus: 1LSB=1°C; PDO ; Type: I16; (raw value:32767 = 328 °C); USS-Adr: 05 06 40 00 hex
2819h 0h
E27
Global
read (2)
Binary outputs: The status of all binary outputs is indicated as binary word. Bit0=BA1 to
Bit9=BA10.
NOTE
Note that an encoder simulation on BA1 and BA2 is not indicated in E27.
Fieldbus: 1LSB=1; PDO ; Type: U16; USS-Adr: 05 06 C0 00 hex
281Bh 0h
E28
Global
read (1)
Analog-output2-level: Indication of the level on the analog output (X1.7 and X1.8). ±10 V
corresponds to ±100 %.
Fieldbus: 1LSB=0,001V; PDO ; Type: I16; (raw value:32767 = 20.000 V); USS-Adr: 05 07 00 00 hex
281Ch 0h
E30
Global
read (1)
Run time: Indication of how long the inverter controller section was supplied with voltage
(operating hours counter).
Fieldbus: 1LSB=1; Type: U32; USS-Adr: 05 07 80 00 hex
281Eh 0h
E31
Global
read (1)
Enable time: Indication of how long the inverter controller section was supplied with voltage and
the power section enable was active.
Fieldbus: 1LSB=1; Type: U32; USS-Adr: 05 07 C0 00 hex
281Fh 0h
E32
Global
read (1)
Energy counter: Indication of the total supplied energy in Wh.
Fieldbus: 1LSB=1Wh; PDO ; Type: U32; USS-Adr: 05 08 00 00 hex
2820h 0h
E33
Global
read (1)
Vi-max-memorized value: The DC link voltage is monitored continuously. The greatest
measured value is stored here non-volatilely. This value can be reset with A371.
Fieldbus: 1LSB=0,1V; PDO ; Type: I16; USS-Adr: 05 08 40 00 hex
2821h 0h
E34
Global
read (1)
I-max-memorized value: The motor current is monitored continuously. The greatest measured
value is stored here non-volatilely. This value can be reset with A371.
Fieldbus: 1LSB=0,1A; PDO ; Type: I16; raw value:1LSB=Fnct.no.3; USS-Adr: 05 08 80 00 hex
2822h 0h