11. Used Parameters
KSW-197
E.. Display Value
Par. Description Fieldbus-
address
E10
Global
read (1)
AE1-Level: Level of the signal available on analog input 1 (X100.1 - X100.3) (without
consideration of F11, F12). To compensate for an offset (the value which arrives at the inverter
when the controller specifies 0 V), this must be entered with the opposite sign in F11.
Fieldbus: 1LSB=0,001V; PDO ; Type: I16; (raw value:32767 = 20.000 V); USS-Adr: 05 02 80 00 hex
280Ah 0h
E11
Global
read (1)
AE2-Level: Level of the signal on analog input 2 (X100.4 - X100.5) (without consideration of F21,
F22). To compensate for an offset (the value which arrives at the inverter when the controller
specifies 0 V), this must be entered in F21 with the opposite sign.
Fieldbus: 1LSB=0,001V; PDO ; Type: I16; (raw value:32767 = 20.000 V); USS-Adr: 05 02 C0 00 hex
280Bh 0h
E14
Global
read (2)
Chargerelay: Status of the internal charging relay. Active means that the relay contact is closed
and the charging resistors from the power network to the DC link are bypassed. When the network
voltage is turned on, the charging relay remains open at first. It closes when the DC link is charged
up via the charging resistors.
NOTE
Make sure that the charging relay contacts are open (E14 = 0:inactive) before you connect the
power supply. Particularly in a DC link network, remember that the charging relays of all connected
inverters are open before the power supply is connected.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 05 03 80 00 hex
280Eh 0h
E15
Global
read (1)
n-motor-encoder: Speed calculated from the motor encoder specified in B26. This indication
also functions when the control type in B20 does not require an encoder.
Fieldbus: 1LSB=0,1rpm; PDO ; Type: I32; (raw value:14 Bit=1·rpm); USS-Adr: 05 03 C0 00 hex
280Fh 0h
E16
Global
read (1)
Analog-output1-level: Indication of the level on the analog output (X100.6 und X100.7). ±10 V
corresponds to ±100 %.
Fieldbus: 1LSB=0,001V; PDO ; Type: I16; (raw value:32767 = 20.000 V); USS-Adr: 05 04 00 00 hex
2810h 0h
E17
Global
read (1)
Relay1: State of relay 1 (ready-for-operation relay, X1.1, X1.2). Active means that the relay
contact is closed. Indicates readiness for operation of the control electronics. There are no faults.
0: inactive;
1: active;
Fieldbus: 1LSB=1; PDO ; Type: B; USS-Adr: 05 04 40 00 hex
2811h 0h
E18
Global
read (1)
Relay 2: State of relay 2 (mechanical halting brake, X2.1, X2.2). Active means that the relay
contact is closed and the halting brake is open.
0: inactive;
1: active;
Fieldbus: 1LSB=1; PDO ; Type: B; USS-Adr: 05 04 80 00 hex
2812h 0h
E19
Global
read (2)
Binary inputs: Indicates status of all binary inputs as binary word.
Fieldbus: 1LSB=1; PDO ; Type: U16; USS-Adr: 05 04 C0 00 hex
2813h 0h
E20
Global
read (1)
Device utilisation: Indicates the current utilization of the inverter in %. 100% corresponds to the
nominal power of the inverter.
Fieldbus: 1LSB=0,1%; PDO ; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 05 05 00 00 hex
2814h 0h
E21
Global
read (1)
Motor utilisation: Indicates current utilization of the motor in %. Reference number is the
nominal motor current entered under B12.
Fieldbus: 1LSB=0,1%; PDO ; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 05 05 40 00 hex
2815h 0h