11. Used Parameters
KSW-189
D.. Reference Value
Par. Description Fieldbus-
address
D400.0
Axis
r=2, w=2
Reverse delay: When the signal reverse delay is to be processed with time delay, a switchon
delay can be parameterized in D400.0 and a switchoff delay can be parameterized in D400.1.
The time is specified in ms.
NOTE
Remember that the delay time may be up to one inverter cycle longer (A150). This happens when
the delay is in the range of the inverter cycle time A150.
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 04 64 00 00 hex
2790h
Array
0h
D400.1
Axis
r=2, w=2
Reverse delay
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 04 64 00 01 hex
2790h
Array
1h
D401.0
Axis
r=2, w=2
External fault delay: When the signal external fault delay is to be processed with time delay, a
switchon delay can be parameterized in D401.0 and a switchoff delay can be parameterized in
D401.1.
The time is specified in ms.
NOTE
Remember that the delay time may be up to one inverter cycle longer (A150). This happens when
the delay is in the range of the inverter cycle time A150.
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 04 64 40 00 hex
2791h
Array
0h
D401.1
Axis
r=2, w=2
External fault delay
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 04 64 40 01 hex
2791h
Array
1h
D402.0
Axis
r=2, w=2
Stop delay: When the signal stop delay is to be processed with time delay, a switchon delay can
be parameterized in D402.0 and a switchoff delay can be parameterized in D402.1.
The time is specified in ms.
NOTE
Remember that the delay time may be up to one inverter cycle longer (A150). This happens when
the delay is in the range of the inverter cycle time A150.
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 04 64 80 00 hex
2792h
Array
0h
D402.1
Axis
r=2, w=2
Stop delay
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 04 64 80 01 hex
2792h
Array
1h
D403.0
Axis
r=2, w=2
Limit switch+ delay: When the signal limit switch+ delay is to be processed with time delay, a
switchon delay can be parameterized in D403.0 and a switchoff delay can be parameterized in
D403.1.
The time is specified in ms.
NOTE
Remember that the delay time may be up to one inverter cycle longer (A150). This happens when
the delay is in the range of the inverter cycle time A150.
Also please remember that the limit switches are evaluated high-active. For this reason, the delay
for the limit switch switchoff (and thus the tripping) is parameterized in parameter element 0 and the
switchon delay is parameterized in element 1.
Value range in ms: 0 ... 0 ... 4294967
Fieldbus: 1LSB=1ms; Type: U32; (raw value:1LSB=0,00099999993131496·ms); USS-Adr: 04 64 C0 00 hex
2793h
Array
0h