11. Used Parameters
KSW-185
D.. Reference Value
Par. Description Fieldbus-
address
D370
Axis
read (2)
RV-acknowledge: The parameter shows the selected reference value combination as decimal-
coded. When this coding is used, a five-position decimal number (e.g., 16245) is indicated.
The 100s position stands for the selected main reference value. The 10s position stands for the
adding reference value and the 1s position stands for the factor reference value.
The reference values are specified with the following numbers:
0: No reference value selected (only possible with adding and factor reference value)
1: Ref value external
2: Preset reference values/fixed values (fixed values only for adding and factor
reference value)
3: Motorized potentiometer
4: Correction reference value 1
5: Correction reference value 2
6: PID control error
7: n-actual
8: Master reference (only for the 100s position)
9: Jog ref value
Example:
105 = ref value external as main reference value (D30). Correction reference value 2 as factor
reference value (D33).
345 = Motorized potentiometer as main reference value (D30). Correction reference value 1 as
adding reference value (D31). Correction reference value 2 as factor reference value (D33).
When the setting D30 = 2 is used (preset reference values as main reference value), the currently
selected preset reference value can be read out in the 1000s and 10000s position.
Example:
8200 = Eight's preset reference value selected as main reference value (D10.7, D11.7)
16205 = Sixteen's preset reference value selected as main reference value (D10.15, D11.15).
Correction reference value 2 selected as factor reference value.
NOTE
The master reference value cannot be set in D30. The signal master/slave switch (D111) must be
used to select the master reference value. For this reason, an active master reference value is
indicated in D370 with the value 800.
Fieldbus: 1LSB=1; PDO ; Type: I16; USS-Adr: 04 5C 80 00 hex
2772h 0h
D371
Axis
read (2)
Preset ref value: The parameter shows the value of the current preset reference value (D11.x).
NOTE
This parameter is shown in user units. The user units are specified in D87 and D88.
Fieldbus: 1LSB=siehe D86; PDO ; Type: I32; raw value:1LSB=Fnct.no.17; USS-Adr: 04 5C C0 00 hex
2773h 0h
D372
Axis
read (2)
Fix ref value: The parameter shows the value of the current fixed value.
NOTE
This parameter is shown in user units. The user units are specified in D87 and D88.
Fieldbus: 1LSB=siehe D86; PDO ; Type: I32; raw value:1LSB=Fnct.no.17; USS-Adr: 04 5D 00 00 hex
2774h 0h
D373
Axis
read (2)
Pre val acc ramp selected: The parameter shows the number of the active preset-reference-
value-accelerating-ramp.
Fieldbus: 1LSB=1; PDO ; Type: U8; USS-Adr: 04 5D 40 00 hex
2775h 0h
D374
Axis
read (2)
Pre val acc ramp value: The parameter shows the value of the active preset-reference-value-
accelerating-ramp.
NOTE
This parameter is indicated in user units per second. The user units are specified in D87 and D88.
Fieldbus: 1LSB=siehe D86; PDO ; Type: I32; raw value:1LSB=Fnct.no.18; USS-Adr: 04 5D 80 00 hex
2776h 0h