11. Used Parameters
KSW-174
D.. Reference Value
Par. Description Fieldbus-
address
D194
Axis
read (1)
Range control 1 red above: D194 is 1:active when the value indicated in D69 is above the
limit entered in D67 (D69 > D67). The application event 1 is triggered at the same time (parameters
U110 to U112).
The signal can be queried in D202 Bit 4 via fieldbus.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 04 30 80 00 hex
26C2h 0h
D195
Axis
read (1)
Range control 2 red below: D195 is 1:active when the value indicated in D79 is below the
limit entered in D74 (D79 < D74). The application event 2 is triggered at the same time (parameters
U120 to U122).
The signal can be queried in D202 Bit 5 via fieldbus.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 04 30 C0 00 hex
26C3h 0h
D196
Axis
read (1)
Range control 2 yellow below: D196 is 1:active when the value indicated in D79 is between
the values D74 and D75 (D74 < D79 < D75).
The signal can be queried in D202 Bit 6 via fieldbus.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 04 31 00 00 hex
26C4h 0h
D197
Axis
read (1)
Range control 2 green: D197 is 1:active when the value indicated in D79 is between the
values D75 and D76 (D75 < D79 < D76).
The signal can be queried in D202 Bit 7 via fieldbus.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 04 31 40 00 hex
26C5h 0h
D198
Axis
read (1)
Range control 2 yellow above: D198 is 1:active when the value indicated in D79 is between
the values D76 and D77 (D76 < D79 < D77).
The signal can be queried in D202 Bit 8 via fieldbus.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 04 31 80 00 hex
26C6h 0h
D199
Axis
read (1)
Range control 2 red above: D199 is 1:active when the value indicated in D79 is above the
limit entered in D77 (D79 > D77). The application event 3 is triggered at the same time (parameters
U130 to U132).
The signal can be queried in D202 Bit 9 via fieldbus.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 04 31 C0 00 hex
26C7h 0h