11. Used Parameters
KSW-165
D.. Reference Value
Par. Description Fieldbus-
address
D119
Axis, OFF
r=1, w=1
Edge enable main ref value source: When the main reference value is switched during
operation, the change must be accepted with an enable signal. The enable can be level or edge-
controlled. To obtain acceptance, either a positive edge must be determined for the signal enable
main ref value (edge) or a HIGH level must be determined for the signal enable main ref value
(level).
The parameter D119 specifies the source for the signal edge enable main ref value. The selections
0:low and 1:high correspond to fixed signal levels. The signal enable main ref value (edge) cannot
be used with these selections. When the selection is 2:parameter, the control word D211 Bit10 is
used as the source. The control word can be written via fieldbus.
Regardless of the source selected, the signal is indicated in D319. If the signal is to be processed
with time delay, a "switch on" delay can be parameterized in D419.0 and a "switch off" delay in
D419.1.
0: Low;
1: High;
2: parameter;
3: BE1;
4: BE1-inverted;
5: BE2;
6: BE2-inverted;
7: BE3;
8: BE3-inverted;
9: BE4;
10: BE4-inverted;
11: BE5;
12: BE5-inverted;
13: BE6;
14: BE6-inverted;
15: BE7;
16: BE7-inverted;
17: BE8;
18: BE8-inverted;
19: BE9;
20: BE9-inverted;
21: BE10;
22: BE10-inverted;
23: BE11;
24: BE11-inverted;
25: BE12;
26: BE12-inverted;
27: BE13;
28: BE13-inverted;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 04 1D C0 00 hex
2677h 0h
D120
Axis, OFF
r=1, w=1
Level enable main ref value source: When the main reference value is switched during
operation, the change must be accepted with an enable signal. The enable can be level or edge-
controlled. To obtain acceptance, either a positive edge must be determined for the signal enable
main ref value (edge) or a HIGH level must be determined for the signal enable main ref value
(level).
The parameter D120 specifies the source for the signal level enable main ref value. The selections
0:low and 1:high correspond to fixed signal levels. When the selection is 2:parameter, the control
word D211 Bit11 is used as the source. The control word can be written via fieldbus.
Regardless of the selected source, the signal is indicated in D320. When the signal is to be
processed with time delay, a "switch on" delay can be parameterized in D420.0 and a "switch off"
delay in D420.1.
0: Low;
1: High;
2: parameter;
3: BE1;
4: BE1-inverted;
5: BE2;
6: BE2-inverted;
7: BE3;
2678h 0h