D.. Reference Value
Par. Description Fieldbus-
address
D102
Axis, OFF
r=1, w=1
Stop source: When the Stop signal is active, the reference value 0 is specified for the drive. The
motor stops.
The parameter D102 specifies the source of the signal. The selections 0:low and 1:high correspond
to fixed signal levels. Control word D210 Bit2 is used as the source for selection 2:parameter. The
control word can be written via fieldbus.
Regardless of the selected source, the signal is indicated in D302. If the signal is to be processed
with a time delay, a "switch on" delay can be parameterized in D402.0 and a "switch off" delay in
D402.1.
0: Low;
1: High;
2: parameter;
3: BE1;
4: BE1-inverted;
5: BE2;
6: BE2-inverted;
7: BE3;
8: BE3-inverted;
9: BE4;
10: BE4-inverted;
11: BE5;
12: BE5-inverted;
13: BE6;
14: BE6-inverted;
15: BE7;
16: BE7-inverted;
17: BE8;
18: BE8-inverted;
19: BE9;
20: BE9-inverted;
21: BE10;
22: BE10-inverted;
23: BE11;
24: BE11-inverted;
25: BE12;
26: BE12-inverted;
27: BE13;
28: BE13-inverted;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 04 19 80 00 hex
2666h 0h
D103
Axis, OFF
r=1, w=1
Limit switch+ source: When the end switch+ signal is active, application event 5 is triggered.
The type of reaction and the text to be displayed can be specified in parameters U150 to U152. The
standard reaction is that the device assumes the "fault" state. The direction after the limit switch is
passed over is blocked. After the fault is acknowledged, the drive can continue in the direction
opposite from the switch.
The parameter D103 specifies the source of the signal. The selections 0:low and 1:high correspond
to fixed signal levels. Control word D210 Bit3 is used as the source for selection 2:parameter. The
control word can be written via fieldbus.
Regardless of the selected source, the signal is indicated in D303. If the signal is to be processed
with a time delay, a "switch on" delay can be parameterized in D403.0 and a "switch off" delay in
D403.1.
0: Low;
1: High;
2: parameter;
3: BE1;
4: BE1-inverted;
5: BE2;
6: BE2-inverted;
7: BE3;
8: BE3-inverted;
9: BE4;
10: BE4-inverted;
11: BE5;
2667h 0h