Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-147
D.. Reference Value
Par. Description Fieldbus-
address
D65
Axis
r=3, w=3
Range control 1 lower limit 1: Range control 1 is defined by parameters D60 to D69. The
result is indicated in D190 to D194.
D65 determines the first lower limit of range control. D191 indicates when this limit has been
dropped below and signals that the value in D69 is approaching the critical limit D64. When the
value in D69 is between D65 and D66, this is indicated by D192.
Value range in %: -800.0 ... -50,0 ... 800.0
Fieldbus: 1LSB=0,1%; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 04 10 40 00 hex
2641h 0h
D66
Axis
r=3, w=3
Range control 1 upper limit 1: Range control 1 is defined by parameters D60 to D69. The
result is indicated in D190 to D194.
D66 determines the first upper limit of range control. D193 indicates when this limit has been
dropped above and signals that the value in D69 is approaching the critical limit D67. When the
value in D69 is between D65 and D66, this is indicated by D192.
Value range in %: -800.0 ... 50,0 ... 800.0
Fieldbus: 1LSB=0,1%; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 04 10 80 00 hex
2642h 0h
D67
Axis
r=3, w=3
Range control 1 upper limit 2: Range control 1 is defined by parameters D60 to D69. The
result is indicated in D190 to D194.
D67 determines the upper limit of range control. If D69 drops above this limit, the display occurs in
D194 and event 61 is triggered. The level of the event can be set in U110 to U112.
Value range in %: -800.0 ... 100,0 ... 800.0
Fieldbus: 1LSB=0,1%; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 04 10 C0 00 hex
2643h 0h
D68
Axis
r=3, w=3
Range control 1 Accel + Enable: Range control 1 is defined by parameters D60 to D69. The
result is indicated in D190 to D194.
D68 can be used to restrict range control to static operation. When 0:inactive is parameterized,
range control is not performed during acceleration procedures or when the enable is switched off.
The result signals D190 to D194 are set to 0:inactive. When D68 is parameterized to 1:active,
range control is performed continuously and D190 to D194 are set accordingly.
0: inactive;
1: active;
Fieldbus: 1LSB=1; Type: B; USS-Adr: 04 11 00 00 hex
2644h 0h
D69
Axis
read (3)
Range control 1 actual value: Range control 1 is defined by parameters D60 to D69. The
result is indicated in D190 to D194.
D69 indicates the value to be controlled after weighting with D61 and low pass filtering with the time
constant D62.
Fieldbus: 1LSB=0,1%; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 04 11 40 00 hex
2645h 0h
D70
Axis
r=3, w=3
Range control 2 source: Range control 2 is defined by parameters D70 to D79. The result is
indicated in D195 to D199.
The parameter to be controlled is entered in D70.
NOTE
Only parameters with the data format I16 can be controlled. If you want to control a speed value in
the format I32, the format must first be changed with the parameters D98.X and D99.X.
Fieldbus: 1LSB=1; Type: U32; raw value:USS-Adr; USS-Adr: 04 11 80 00 hex
2646h 0h
D71
Axis
r=3, w=3
Range control 2 factor: Range control 2 is defined by parameters D70 to D79. The result is
indicated in D195 to D199.
The
parameter entered in D70 can be weighted in D71. An entry of 25% corresponds to a factor of 1.
Value range in %: -800.0 ... 25,0 ... 800.0
Fieldbus: 1LSB=0,1%; Type: I16; (raw value:32767·LSB=800,0%); USS-Adr: 04 11 C0 00 hex
2647h 0h