Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-125
C.. Machine
Par. Description Fieldbus-
address
C233
Global
r=2, w=2
Torque limit generating: In contrast to absolute torque limitation, a maximum motor and
generator torque can be specified with speed control. C233 is read with the setting C133 =
4:Parameter. This parameter can be written in fieldbus mode.
The current value of the signal torque limit generating can be viewed in C333 regardless of the
selected source.
NOTE
The motor and generator torque limitation is active when the display parameters C332 and C333
have a value other than zero.
Value range in %: 0 ... 150 ... 200
Fieldbus: 1LSB=1%; Type: I16; (raw value:32767·LSB=200%); USS-Adr: 03 3A 40 00 hex
24E9h 0h
C330
Axis
read (2)
Torque limit: Indication of the value of the Torque Limit signal on the interface for calculation of
the torque limits.
The internal, currently effective torque limits also depend on the fixed torque limits C03 and C05 as
well as any possible torque limit due to the i²t model. The current limits are indicated in E62 and
E66.
Fieldbus: 1LSB=1%; PDO ; Type: I16; (raw value:32767·LSB=200%); USS-Adr: 03 52 80 00 hex
254Ah 0h
C331
Axis
read (2)
Torque limit 2: The source of the signal torque limit 2 is set in C131. When an absolute torque
limit is used, torque limit 2 is used as the second limit. When a binary signal (D110) is used, you
can switch between the sources selected in C130 and C131 and a hard startup can be
implemented.
The current value of the signal torque limit 2 can be viewed in C331 regardless of the selected
source.
The torque limits which are currently in effect internally also depend on the fixed torque limits C03
and C05 as well as on a possible torque limit by the i²t model. The current limits are shown in E62
and E66.
Fieldbus: 1LSB=1%; PDO ; Type: I16; (raw value:32767·LSB=200%); USS-Adr: 03 52 C0 00 hex
254Bh 0h
C332
Axis
read (2)
Torque limit motoring: In contrast to absolute torque limitation, a maximum motor and
generator torque can be specified when speed control is used.
The current value of the signal torque limit motoring can be viewed in C332 regardless of the
sources selected in C132.
NOTE
The motor and generator torque limit is active when the display parameters C332 and C333 contain
a value other than zero.
Fieldbus: 1LSB=1%; PDO ; Type: I16; (raw value:32767·LSB=200%); USS-Adr: 03 53 00 00 hex
254Ch 0h
C333
Axis
read (2)
Torque limit generating: In contrast to absolute torque limitation, a maximum motor and
generator torque can be specified when speed control is used.
The current value of the signal torque limit generating can be viewed in C333 regardless of the
sources selected in C133.
NOTE
The motor and generator torque limit is active when the display parameters C332 and C333 contain
a value other than zero.
Fieldbus: 1LSB=1%; PDO ; Type: I16; (raw value:32767·LSB=200%); USS-Adr: 03 53 40 00 hex
254Dh 0h