Specifications

Comfort Reference Value – 5th Generation of STÖBER Inverters
STÖBER
ANTRIEBSTECHNIK
11. Used Parameters
KSW-123
C.. Machine
Par. Description Fieldbus-
address
C37
Axis
r=3, w=3
Reference torque filter: The torque reference value is generated on the output of the speed
controller from two components whose relationship is affected by C37.
Direct output of the PI speed controller (share corresponds to 100%-C37).
Smoothed output of PI speed controller (share corresponds to C37).
For maximum dynamics, set C37=0%. The reference value low pass is cancelled out with the time
constant C36. C37 can be increased to 100% to attenuate the vibrations.
Value range in %: 0 ... 25 ... 100
Fieldbus: 1LSB=1%; Type: I16; (raw value:32767·LSB=100%); USS-Adr: 03 09 40 00 hex
1 Only with control types with current control (B20 = 64:Servo or 2:VC).
2425h 0h
C40
Axis
r=2, w=2
n-window: With applications without brake control (e.g., fast reference value), "standstill reached"
is valid within a window of ±C40. This signal means "quick stop concluded" for the device controller.
Value range in rpm: -8191 ... 30 ... 8191
Fieldbus: 1LSB=1rpm; Type: I16; (raw value:32767 = 8191 rpm); USS-Adr: 03 0A 00 00 hex
2428h 0h
C61
Axis
r=3, w=3
Speed limiter: Switches the speed limiter on. The inverter then still only limits the maximum
speed and is in torque mode.
0: inactive; Normal speed control (possible with higher-level position control, see C62).
1: active; Torque control with speed limiter.
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 03 0F 40 00 hex
1 Only with control types with current control (B20 = 64:Servo or 2:VC).
243Dh 0h
C62
Axis
r=3, w=3
Position ctrl: Switch position control on and off. Position control is used, for example, for
positioning or precise-angle synchronous operation. With all positioning applications (also without
encoder), C62=1 is required.
0: inactive;
1: active; position control
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 03 0F 80 00 hex
243Eh 0h
C130
Axis, OFF
r=2, w=2
Torque limit source: Selection of the source for the signal of the external torque limit "M-Max."
It can be permanently specified that the signal is supplied by the analog inputs or the fieldbus.
With C130=4:Parameter, the (global) parameter C230 is used as the signal source. The resulting
torque limit is indicated in C330.
0: 0 (zero);
1: AE1;
2: AE2;
3: AE3;
4: parameter;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 03 20 80 00 hex
2482h 0h
C131
Axis, OFF
r=2, w=2
Torque limit 2 source: The source of the signal torque limit 2 is set in C131. When there is an
absolute torque limit, torque limit 2 is used as the second limit. When a binary signal (D110) is
used, you can switch between the sources selected in C130 and C131 and a hard startup can be
implemented.
With the setting C131 = 4:parameter, the parameter C231 is used as the source. It can be written
by fieldbus.
The current value of the signal can be viewed in C331 regardless of the source selected.
0: 0 (zero);
1: AE1;
2: AE2;
3: AE3;
4: parameter;
Fieldbus: 1LSB=1; Type: U8; USS-Adr: 03 20 C0 00 hex
2483h 0h