Product manual
EAP01 - Product Manual
5 Commissioning the EAP01
For operational details refer to your system specific documentation; see Table 5 (page 48).
L
The following details are correct for the current VAR Router, DAU, and ACU software versions
at the time of publication:
• VAR Router: CP 4.1.471
• Intellevac DAU: CP V1.5.124
• Intellevac ACU: CP V1.5.115
• VAR8: CP V1.5.124
• VAR8-ACU: CP V1.5.115
If any difficulties are encountered, then refer to Application Solutions (Safety and Security) Ltd.
for advice quoting the software version of your system. The software version is displayed via
the Configuration→System→Misc→Software menu.
Configure the EAP01 from the Router Configuration Tool, or system front panel as described in the following
sections.
5.1 Obtaining the Router’s Input Number
Check the system design documentation to find the Router audio input number being used for the EAP01.
This input number will be required throughout this commissioning procedure, being referred as nn.
For BS5839 Pt.8 compliance the EAP01 should be connected to Router’s inputs 1 or 2, which
operate in the All-Call failsafe override mode in the event of processor failure.
!
!
5.2 Configuring the Microphone Type
Menu: ConfigurationÆSystemÆRouterÆInputsÆMic/LineÆ<I/P #nn – input name>
Where nn is the Router input number found in Section “5.1 Obtaining the Router’s Input Number” (page 25).
Configure the EAP01 as Fire Microphone.
Issue: 02 complete, approved
Page 25 of 52