5.5 Non-Supervised Input
If the requirement is to detect ON/ OFF signal and line fault monitoring is not required,
non-supervised mode may be used. To enable this mode, set DIP SW 1 and Switch 6
(LSS) should be turned “OFF”. No end of line resistor is required.
Non-supervised input setting can detect 2 states:
State
Function
Normal (Device in NC)
Normal condition
Activate (Device activates in open circuit)
Input line is triggered
Note: Setting of this switch applies to all analog 8 inputs. If there is any input requires
line supervision, then ALL inputs have to operate in the same mode. This setting has
no effect on Fire Alarm input.
5.6 P908 Input Setting
When P908 is configured as access control, the following default input settings applies:
Input
Header
Default Function
For
Input 1
INPUT
Exit Button Reader 1
Input 2
Door Sensor Reader 1
Input 3
Exit Button Reader 2
Input 4
Door Sensor Reader 2
Input 5
Exit Button Reader 3
Input 6
Door Sensor Reader 3
Input 7
Exit Button Reader 4
Input 8
Door Sensor Reader 4