30
6.3.2 48 VDC
The 48 VDC (42 – 56 VDC) power input includes a fuse on the 48 VDC input to protect
against overload. The IPBL also has a protection circuit to protect both the IPBL and the
external power supply from damages caused by the user reversing the input terminals
during installation.
Figure 26 .
Figure 18. Pinning of the 48 VDC power supply
Note: A ground cable must be fastened to the protective earth (3) when 48 VDC is used
as power source.
1 Fasten the ground cable to the protective earth (3) using the attached M4 screw
(Philips) and washer.
2 Cut the power cable to the correct length.
The recommended wire size diameter is 1 mm (18 AWG).
3 Attach the positive lead to (1).
4 Attach the negative lead to (2).
5 Connect the power cable to 48 VDC power source.
The IPBL is switched on.
12