Troubleshooting guide
TD 92735EN
15 May 2012 / Ver. G
Installation and Operation Manual
Unite Connectivity Manager
216
Cold-storage room 1, door open
Input Triggers: “Cold-storage door open” and “Cold-storage door still open”
When the door has been open for 2 minutes (120 seconds), the action is started. The action
shall not be repeated so the “Repetition time” is not stated and the value in the “Max. No. of
Repetitions” field has no meaning.
When the door has been open for 10 minutes (600 seconds), another message is sent as a
reminder. A separate Alarm Action is required if a different beep-code is desired.
Actions Activate Output Action and Send Message Actions
Figure 102. Alarm Action, Cold-storage room open.
For Activate Output Action, the duration is here set to max value 3600.
Figure 93.