Product Overview

303
Visit our website at ASCO.com or contact us at (800) 972-2726
2/2
SERIES
S262
COMBUSTION
Features
2-way normally open operation
Die-cast aluminum bodies
Zero differential piloted diaphragm
Valves provided with 1/8" NPT pipe taps with plug
for routine testing
Broad ambient temperature range -20˚F up to 170˚F
NO
Construction
Fluid
Fuel Gas
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Core Tube 305 Stainless Steel
Core and Plugnut 430F Stainless Steel
Core Guide Acetal
Springs 302F Stainless Steel
Shading Coil Copper
Pipe Plug Zinc-Plated Steel
Standard Coil
and Class of
Insulation
Watt Rating and
Power Consumption
Ambient
Temp.°F
Spare Coil
Family
AC Explosionproof
Watts
VA
Holding
VA
Inrush AC
F 10.5 26 66 -20 to 167 (-29 to 75) 529027
F 15.4 34 162 -20 to 170 (-29 to 77) 529029
F 28.2 55 451 -20 to 170 (-29 to 77) 529031
Standard Voltages: 120 volts, AC 60 Hz
Optional Voltages: 24, 240 volts AC, 60 Hz
S262 catalog number includes codification for voltage. However voltage must be
specified when ordering spare coil.
Electrical
Solenoid Enclosures
Standard: Type 1 General Purpose Junction Box
Housing with two 7/8" knock-outs.
Valve Response Time
Opening Time: Less than 1 second
Closing Time: Less than 1 second
Close-off Pressure
50 psi (3.5 bar) maximum
Approvals
UL listed to standard 429 “Electrically Operated Valves,”
Guide YIOZ, File MP932 General Purpose Valves.
FM Approved to Class 7400 “Liquid and Gas Safety
Shutoff Valves”
CSA Certified to Automatic Gas Valves ANSI Z21.21,
CSA 6.5 (meets standard C22.2 No. 139 “Electrically
Operated Valves”), File 112872
ASCO™ Gas Vent Valves
Pilot Operated | 3/8" - 3" NPT
^ #