373
Visit our website at ASCO.com or contact us at (800) 972-2726
2/2
SERIES
S261
COMBUSTION
Features
2-way normally closed operation
Die-cast aluminum bodies
Zero differential piloted diaphragm
For on-off control of fuel gas in commercial and
industrial gas burners
Valves provided with 1/8" NPT upstream and
downstream pipe taps with plug for routine testing
Broad ambient temperature range -20˚F up to 170˚F
N
C
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Core Tube 305 Stainless Steel
Core and Plugnut 430F Stainless Steel
Core Guide CA
Springs 302F Stainless Steel
Shading Coil Copper
Pipe Plug Zinc-Plated Steel
Standard Coil
and Class of
Insulation
Watt Rating and
Power Consumption
Ambient
Temp.°F
Spare Coil
Family
AC Explosionproof
Watts
VA
Holding
VA
Inrush AC
F 10.5 21 69 -20 to 167 (-29 to 75) 529027
F 15.4 27 162 -20 to 170 (-29 to 77) 529029
F 28.2 55 451 -20 to 170 (-29 to 77) 529031
Standard Voltages: 120 volts, AC 60 Hz
Optional Voltages: 24, 240 volts AC, 60 Hz
S261 catalog number includes codification for voltage. However voltage must be
specified when ordering spare coil.
Electrical
Construction
^ #
Fluid
Fuel Gas
Solenoid Enclosures
Standard: Type 1 General Purpose Junction Box
Housing with two 7/8" knock-outs.
Valve Response Time
Opening Time: Less than 1 second
Closing Time: Less than 1 second
Close-off Pressure
50 psi (3.5 bar) maximum
Approvals
UL listed to standard 429 “Electrically Operated Valves,”
Guide YIOZ, File MP932 Safety Valves.
FM Approved to Class 7400 “Liquid and Gas Safety
Shutoff Valves”
CSA Certified to Automatic Gas Valves ANSI Z21.21,
CSA 6.5 C/I (meets standard C22.2 No. 139
“Electrically Operated Valves”), File 112872
ASCO™ Gas Shutoff Valves
Pilot Operated | 3/8" - 3" NPT

Summary of content (4 pages)