Submittal Sheet
4
2/2
SERIES
K3A7
COMBUSTION
Features
• 2-way normally closed operation
• Die-cast aluminum bodies
• For on-off control of fuel gas in commercial and
industrial gas burners
• Valves provided with 1/8" NPT upstream and
downstream pipe tap with plug for routine testing
• Suitable for ambient temperatures up to 175˚F
Medium Pressure Direct Acting
Gas Shutoff Valves
1 1/4" and 1 1/2" NPT
NC
395
Valve Response Time
Opening Time: Less than 1 second; Closing Time: Less than 1 second
Solenoid Enclosures
Standard: Type 1 General Purpose Junction Box housing with two
7/8" knockouts.
Approvals
UL listed to standard 429 “Electrically Operated Valves,”
Guide YIOZ, File MP932 Safety Valves.
CSA Certified to:
1) Standard C22.2 No. 139 “Electrically Operated
Valves,” File 113070.
2) Automatic Gas Valves Z21.21 (6.5), File 109157
and 113070.
3) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 113070.
Valve Parts in Contact with Fluids
Body Aluminum
Seals and Disc NBR
Washer 302 Stainless Steel
Core Tube 305 Stainless Steel
Core and Plugnut 430F Stainless Steel
Core Guide CA
Springs 302F Stainless Steel
Shading Coil Copper
Pipe Plug Zinc-Plated Steel
Standard
Coil and
Class of
Insulation
Watt Rating and
Power Consumption
Ambient
Temp.°F
Spare Coil Family
AC General Purpose Explosionproof
Watts
VA
Holding
VA
Inrush AC AC
F 20 43 240 -40 to 175 222345 -
Standard Voltages: 24, 120, 240 volts AC, 60 Hz.
K3A catalog number includes codification for voltage. However, voltage must be
specified when ordering spare coil.
Electrical
Construction
^