Product Overview
2/2
SERIES
8214
(200)
4
338
COMBUSTION
Specifications - Standard (English units)
Pipe
Size
(in)
Orifice
Size
(mm)
Kv
Flow
Factor
Flow
Capacity x
Fuel Gas
Capacity x
Operating Pressure
Differential (bar)
Max. Fluid
Temp.°C
Catalog
Number
Const.
Ref.
Agency
Watt Ratting/
Class of Coil
Insulation
Approx.
Shipping
Weight (kgs)
(m
3
/hr) Btu/hr Min. Max. AC DC AC
DC
UL FM CSA AC DC
GENERAL PURPOSE
3/4 41 9.4 17 593,200 0 0.3 52 - 8214 235 1
-
H
-
H
20/F - 2.3
1 41 17.9 32 1,132,300 0 0.3 52 - 8214 250 1
-
H
-
H
20/F - 2.3
1 1/4 41 27.3 49 1,725,500 0 0.3 52 - 8214 260 1
-
H
-
H
20/F - 2.2
1 1/2 41 29.9 53 1,887,200 0 0.3 52 - 8214 270 1
-
H
-
H
20/F - 2.1
1 1/4
(High Flow)
53 30.7 55 1,925,000 0 0.3 52 - 8214 265 2
-
H
-
H
20/F - 3.1
1 1/2
(High Flow)
53 38.4 68 2,406,000 0 0.3 52 - 8214 275 2
-
H
-
H
20/F - 2.9
2 53 46.9 83 2,940,500 0 0.3 52 - 8214 280 2
-
H
-
H
20/F - 2.8
2
(High Flow)
76 64.0 115 4,044,100 0 0.3 52 52 8214 285 3 16
H
-
H
20/H 35.1/F 6.0
2 1/2 76 88.7 159 5,607,800 0 0.3 52 52 8214 290 3 16
H
-
H
20/H 35.1/F 5.7
3 76 89.6 160 5,661,700 0 0.3 52 52 8214 240 3 16
H
-
H
20/H 35.1/F 5.3
WATERTIGHT
3/4 41 9.4 17 593,200 0 0.3 52 52 8214G236 4 4A
H
-
H
20.1/F 15.8/F 2.3
1 41 17.9 32 1,132,300 0 0.3 52 52 8214G251 4 4A
H
-
H
20.1/F 15.8/F 2.3
1 1/4 41 27.3 49 1,725,500 0 0.3 52 52 8214G261 4 4A
H
-
H
20.1/F 15.8/F 2.2
1 1/2 41 29.9 53 1,887,200 0 0.3 52 52 8214G271 4 4A
H
-
H
20.1/F 15.8/F 2.1
1 1/4
(High Flow)
53 30.7 55 1,925,000 0 0.3 52 52 8214G266 5 5A
H
-
H
20.1/F 15.8/F 3.1
1 1/2
(High Flow)
53 38.4 68 2,406,000 0 0.3 52 52 8214G276 5 5A
H
-
H
20.1/F 15.8/F 2.9
2 53 46.9 83 2,940,500 0 0.3 52 52 8214G281 5 5A
H
-
H
20.1/F 15.8/F 2.8
H = Safety Shutoff Valve. x 1” W.C. Drop @ 2” W.C. Inlet Pressure, 1,000 Btu/cu.ft. or more, 0.64 Specific Gravity
Specifications - Standard (Metric units)
Pipe
Size
(in)
Orifice
Size
(in)
Cv
Flow
Factor
Flow
Capacityx
Fuel Gas
Capacityx
Operating Pressure
Differential (psi)
Max. Fluid
Temp.°F
Catalog
Number
Const.
Ref. Agency
Watt Ratting/
Class of Coil
Insulation
Approx.
Shipping
Weight (lbs)
ft
3
/hr Btu/hr Min. Max. AC DC AC
DC
UL FM CSA AC DC
GENERAL PURPOSE
3/4 1 5/8 11 593 593,200 0 5 125 - 8214 235 1
-
H
-
H
20/F - 5.1
1 1 5/8 21 1132 1,132,300 0 5 125 - 8214 250 1
-
H
-
H
20/F - 5.0
1 1/4 1 5/8 32 1726 1,725,500 0 5 125 - 8214 260 1
-
H
-
H
20/F - 4.9
1 1/2 1 5/8 35 1887 1,887,200 0 5 125 - 8214 270 1
-
H
-
H
20/F - 4.7
1 1/4
(High Flow)
2 3/32 36 1925 1,925,000 0 5 125 - 8214 265 2
-
H
-
H
20/F - 6.9
1 1/2
(High Flow)
2 3/32 45 2406 2,406,000 0 5 125 - 8214 275 2
-
H
-
H
20/F - 6.6
2 2 3/32 55 2941 2,940,500 0 5 125 - 8214 280 2
-
H
-
H
20/F - 6.2
2
(High Flow)
3 75 4044 4,044,100 0 5 125 125 8214 285 3 16
H
-
H
20/H 35.1/F 13.1
2 1/2 3 104 5608 5,607,800 0 5 125 125 8214 290 3 16
H
-
H
20/H 35.1/F 12.6
3 3 105 5662 5,661,700 0 5 125 125 8214 240 3 16
H
-
H
20/H 35.1/F 11.7
WATERTIGHT
3/4 1 5/8 11 593 593,200 0 5 125 125 8214G236 4 4A
H
-
H
20.1/F 15.8/F 5.1
1 1 5/8 21 1132 1,132,300 0 5 125 125 8214G251 4 4A
H
-
H
20.1/F 15.8/F 5.0
1 1/4 1 5/8 32 1726 1,725,500 0 5 125 125 8214G261 4 4A
H
-
H
20.1/F 15.8/F 4.9
1 1/2 1 5/8 35 1887 1,887,200 0 5 125 125 8214G271 4 4A
H
-
H
20.1/F 15.8/F 4.7
1 1/4
(High Flow)
2 3/32 36 1925 1,925,000 0 5 125 125 8214G266 5 5A
H
-
H
20.1/F 15.8/F 6.9
1 1/2
(High Flow)
2 3/32 45 2406 2,406,000 0 5 125 125 8214G276 5 5A
H
-
H
20.1/F 15.8/F 6.6
2 2 3/32 55 2941 2,940,500 0 5 125 125 8214G281 5 5A
H
-
H
20.1/F 15.8/F 6.2
H = Safety Shutoff Valve. x 1” W.C. Drop @ 2” W.C. Inlet Pressure, 1,000 Btu/cu.ft. or more, 0.64 Specific Gravity Gas.