Submittal Sheet
2/2
SERIES
H118
4
COMBUSTION
358
Replacement Actuators:
Replacement Switches:
Catalog Number
Voltage
H10A620B5F1 120V/60Hz
H10A640B5F1
240V/60Hz
H30A2220B20F1
120V/60Hz
For FM Proof of Closure ad F26 to Cat. No.
4" size only
Kits Switches* Type
1" Through 3"
S104772EA1 1
Auxiliary
(Adjustable)
S104772EA2
2
S104772EA3
3
S104772EAX1 1 Proof of Closure
4" Only
S104772FA1
1
Auxiliary
(Adjustable)
S104772FA2 2
S104772FA3
3
S104772FAX1
1 Proof of Closure
* Yoke Mounted
Specifications (English units)
Pipe
Size
(in)
Cv
Flow
Factor
Gas
Capacity
Operating Pressure
Differential (psi)
Max.
Fluid
Temp.°F
Catalog Number
Const.
Ref.
Agency
Opening
Time (Sec.)
Approx.
Shipping
Weight
(lbs)
Cu. Ft/hr. Min. Max. UL FM CSA
COMBUSTION (Fuel Gas) - Normally Closed
Standard Trim
1 17 915 0 35 150 H118AF122F1 1
7-18 22
1 1/4 25 1,155 0 35 150 H118AG122F1 1
7-18 23
1 1/2 35 1,525 0 25 150 H118AH122F1 2
8-20 28
2 67 3,300 0 15 150 H118AJ122F1 3
10-24 32
2 1/2 86 3,730 0 15 150 H118AK122F1 4
11-28 52
3 125 6,095 0 15 150 H118AL122F1 5
12-18 54
4 (Flange)
168 9,710 0 15 150 H118AN132F1 6
15-24 148
Valve Seal Overtravel Trim (Proof of Closure)
2 67 3,300 0 15 150 H118AJ122F1F26V16 3
9-17 37
2 1/2 86 3,730 0 15 150 H118AK122F1F26V16 4
11-20 57
3 125 6,095 0 15 150 H118AL122F1F26V16 5
13-23 59
4 (Flange)
168 9,710 0 15 150 H118AN132F1F26V16 6
15-24 153
= Safety Shutoff Valve. One cu. ft/hr = 1,000 Btu/hr, 0.64 Specific Gravity Gas @ 1” W.C.P.D.
Type 4/7 Watertight/Explosionproof chage 5th digit to “B” (EX: H118BF112F1). 240V/60Hz change 9th digit to “4” (EX: H118AF124F1) - 1" through 3" only.
Specifications (Metric units)
Pipe
Size
(in)
Kv
Flow
(m
3
/hr)
Gas
Capacity
Operating Pressure
Differential (bar)
Max.
Fluid
Temp.°C
Catalog Number
Const.
Ref.
Agency
Opening
Time (Sec.)
Approx.
Shipping
Weight
(kgs)
Cu. Ft/hr. Min. Max. UL FM CSA
COMBUSTION (Fuel Gas) - Normally Closed
Standard Trim
1 14 915 0 2.4 66 H118AF122F1 1
7-18 10
1 1/4 21 1,155 0 2.4 66 H118AG122F1 1
7-18 10.5
1 1/2 30 1,525 0 1.7 66 H118AH122F1 2
8-20 12.7
2 57 3,300 0 1 66 H118AJ122F1 3
10-24 14.5
2 1/2 73 3,730 0 1 66 H118AK122F1 4
11-28 23.6
3 106 6,095 0 1 66 H118AL122F1 5
12-18 24.5
4 (Flange)
143 9,710 0 1 66 H118AN132F1 6
15-24 67.3
Valve Seal Overtravel Trim (Proof of Closure)
2 57 3,300 0 1 66 H118AJ122F1F26V16 3
9-17 16.8
2 1/2 73 3,730 0 1 66 H118AK122F1F26V16 4
11-20 25.9
3 106 6,095 0 1 66 H118AL122F1F26V16 5
13-23 26.8
4 (Flange)
143 9,710 0 1 66 H118AN132F1F26V16 6
15-24 69.5
= Safety Shutoff Valve. One cu. ft/hr = 1,000 Btu/hr, 0.64 Specific Gravity Gas @ 1” W.C.P.D.
Type 4/7 Watertight/Explosionproof chage 5th digit to “B” (EX: H118BF112F1). 240V/60Hz change 9th digit to “4” (EX: H118AF124F1) - 1" through 3" only.