Install Instructions

Page 1 of 5 (Section 1 of 2)
All Rights Reserved.
E218586--- 06/11
ASCO Valves
E
ASCO Valve, Inc.
R
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com
R
Installation & Maintenance Instructions
SERIES
I&M No.V9575R4
2--WAY DIRECT-- ACTING SOLENOID VALVES
BRASS OR STAINLESS STEEL CONSTRUCTION -- 1/8I, 1/4I, OR 3/8I PIPE THREADS
8262
8263
NORMALLY OPEN OR NORMALLY CLOSED OPERATION
REVISION “H” & “R”
(Section 1 of 2)
IMPORTANT: See separate solenoid installation and maintenance
instructions for information on: Wiring, Solenoid Temperature,
Causes of Improper Operation, and Coil or Solenoid Replacement.
DESCRIPTION
Series 8262 and 8263 valves are 2 --- way direct---acting general
service solenoid valves. Valves bodies are of rugged brass or
stainless steel. Series 8262 or 8263 valves may be provided with a
watertight/explosionproof solenoid enclosure.
OPERATION
Normally Open: Valve is open when solenoid is de--- energized;
closed when energized.
Normally Closed: Valve is closed when solenoid is de---energized;
open when energized.
IMPORTANT: No minimum operating pressure required.
Manual Operation (Valves with Suffix MS)
Manual operator allows manual operation when desired or during
an electrical power outage.
To engage manual operator, rotate stem on the side of the body
clockwise until it hits a stop, approximately 90_ from its original
position. Do NOT rotate beyond stops. Do NOT apply excessive
force beyond stops. Valve will now be in the same position as when
thesolenoidis energized. To disengage,rotate stem counterclockwise
until it hits a stop, approximately 90_ from its original position. Do
NOT rotate beyond stops. Do NOT apply excessive force beyond
stops.
MS option is not available on normally closed valves that have a
pressure rating greater than 750 PSI. MS option is not available on
normally open valves.
CAUTION: Do NOT rotate beyond 90
_
__
_
stops. Do NOT apply
excessive force beyond stops. Rotating beyond the 90
_
__
_
stops could
result in equipment damage.
CAUTION: For valve to operate electrically, manual operator
stem must be fully rotated counterclockwise.
INSTALLATION
Check nameplate for correct catalog number, pressure, voltage,
frequency, and service. Never apply incompatible fluids or exceed
pressure rating of the valve. Installation and valve maintenance to
be performed by qualified personnel.
Note: Inlet port will either be marked “1 or “IN”. Outlet port will
be marked 2 or “OUT. (see Figure 1)
Future Service Considerations.
Provision should be made for performing seat leakage, external
leakage, and operational tests on the valve with a
nonhazardous,noncombustible fluid after disassembly and
reassembly.
Temperature Limitations
For maximum valve ambient and fluid temperatures, refer to the
following tables. Use catalog number, coil prefix, suffix, and watt
rating on nameplate to identify the maximum ambient and fluid
temperatures.
NOTE: The following Temperature Limitations Tables do not
apply to Magnetic Latch Valves: Catalog Numbers 8262A610 to
8262A627; 8263A615 to 8263A618, and 8263A624 to 8263A627.
See separate Instruction Manual.
Max. Ambient Temperature Limitations for AC and DC Coil Valves,
Catalog Numbers 8262H/R & 8263H/R
Prefix
1
Coil
Class
Watt Ratings
Max Ambient
Temperature
AC
DC
Normally
Closed
Normally
Open
60Hz 50Hz _C _F _C _F
EF,EV FT 6.1, 10.1 8.1, 10.1
---
52 125
52 125
EF,EV FB 9.1, 17.1 11.1, 17.1
--- --- ---
FT 6.1, 10.1 8.1, 10.1
---
55 131
55 131
FB 9.1, 17.1 11.1, 17.1
--- --- ---
HT
--- ---
10.6, 11.6
40
2
104
2
55 131
HB
--- ---
22.6, 18.6
EF,EV HT
--- ---
10.6, 11.6
EF,EV HB
--- ---
22.6, 18.6
HT 6.1, 10.1 8.1, 10.1
---
60 140
60 140
HB 9.1, 17.1 11.1, 17.1
---
55 131
EF,EV HT 6.1, 10.1 8.1, 10.1
---
60 140
EF,EV HB 9.1, 17.1 11.1, 17.1
--- --- ---
---
2
2 2
60 140
Max. Ambient Temperature Limitations for AC and DC Coil Valves,
Catalog Numbers 8262H/R & 8263H/R
Valve
Elastomer
/Suffix
Coil
Class
Watt Ratings
Max. Fluid
Temp.
AC
DC
60Hz 50Hz
_C _F
UR/None
4
FT, FB,
HT, HB
5
6.1, 10.1,
9.1, 17.1,
2
8.1, 10.1,
11.1,
17.1, 2
10.6,
11.6,
18.6,
22.6, 2
60 140
NBR/
None
4
82
5
180
5
CR/J
Lt --- Nitrile/A 75 167
EPDM/E
99
5
210
5
FKM/V &
PTFE/T
FT 6.1, 10.1 8.1, 10.1 ---
99
3
210
3
FB 11.1, 17.1 ---
HT with
EF/EV
Prefix
6.1, 10.1 8.1, 10.1 10.6, 11.6
HB with
EF/EV
Prefix
9.1, 17.1 11.1, 17.1 18.6, 22.6
HT 6.1, 10.1 8.1, 10.1 10.6, 11.6
121
3
5
250
3
5
HB
5
9.1, 17.1 11.1, 17.1 18.6, 22.6
--- 2 2 2
1
=EF, EV data applies to Explosionproof coils only.
temperature of 99_
__
_C/210_
__
_F.
099, 106, 107, 154, 155, 159, 161, 167, 168, 173, 175, 176, 180, 181,
198, 199, 200, 214 and 8262R107, 181, 155, 161, 168, 169.
ambient temperature of 55_C / 131_ F with reduced pressure ratings.
See page 5 of 5, Section 2 of 2 for maximum operating pressure
differential.
3
=Solenoid coils with prefix EF & EV are limited to a maximum fluid
2=
DC Normally closed solenoid valves can be operated at maximum
4=
Urethane (UR) elastomer applies to catalog numbers 8262H079, 089, 096
5
=Normally open 8262H & 8263H valves fitted with HB 17.1 watt AC coils
have a maximum fluid temperature of 75_
__
_C(167_
__
_F)