Submittal Sheet
2/2
SERIES
8221
4
2-WAY
19
Specifications (Metric units)
Pipe
Size
(ins.)
Orifice
Size
(mm)
Kv Flow
Factor
(m3/h)
Operating Pressure
Differential (bar)
Max. Fluid
Temp. ˚C
Brass Body
Const.
Ref.
Watt Rating/
Class of Coil
Insulation
Min.
Max. AC Max. DC
Water Water
AC DC Catalog Number AC DC
NORMALLY CLOSED (Closed when de-energized)
3/8 14 2.57 0.3 10 9 82 65 8221G001 1 6.1/F 11.6/F
1/2 14 3.00 0.3 10 9 82 65 8221G003 1 6.1/F 11.6/F
3/4 19 4.71 0.3 10 9 82 65 8221G005 2 6.1/F 11.6/F
1 25 9.86 0.3 10 9 82 65 8221G007 5 6.1/F 11.6/F
1 1/4 29 11.14 0.3 10 9 82 65 8221G009 6 6.1/F 11.6/F
1 1/2 32 20.57 0.3 10 9 82 65 8221G011 7 6.1/F 11.6/F
2 44 30.86 0.3 10 9 82 65 8221G013 11 6.1/F 22.6/F
2 1/2 44 32.57 0.3 10 9 82 65 8221G015 12 6.1/F 22.6/F
NORMALLY OPEN (Open when de-energized)
3/8 14 2.57 0.3 - 9 - 65 8221 021 15 - 16.8/F
3/8 14 2.57 0.3 10 - 82 - 8221G021 3 16.1/F -
1/2 14 3.00 0.3 - 9 - 65 8221 023 15 - 16.8/F
1/2 14 3.00 0.3 10 - 82 - 8221G023 3 16.1/F -
3/4 19 4.71 0.3 - 9 - 65 8221 025 16 - 16.8/F
3/4 19 4.71 0.3 10 - 82 - 8221G025 4 16.1/F -
1 25 9.86 0.3 - 9 - 65 8221 027 17 - 16.8/F
1 25 9.86 0.3 10 - 82 - 8221G027 8 16.1/F -
1 1/4 29 11.14 0.3 - 9 - 65 8221 029 18 - 16.8/F
1 1/4 29 11.14 0.3 10 - 82 - 8221G029 9 16.1/F -
1 1/2 32 20.57 0.3 - 9 - 65 8221 031 19 - 16.8/F
1 1/2 32 20.57 0.3 10 - 82 - 8221G031 10 16.1/F -
2 44 30.86 0.3 - 9 - 65 8221 033 20 - 16.8/F
2 44 30.86 0.3 10 - 82 - 8221G033 13 16.1/F -
2 1/2 44 32.57 0.3 - 9 - 65 8221 035 21 - 16.8/F
2 1/2 44 32.57 0.3 10 - 82 - 8221G035 14 16.1/F -
Valves require a 0.3 bar Minimum Pressure Differential to open. Once open, they remain open with 0.2 bar differential pressure.
Refer to Steam/Hot Water Valve Series for Hot Water constructions.
On 50 hertz service, the watt rating for the 6.1/F solenoid is 8.1 watts.
Response time upon energization: 3/8" - 1/2" (2-4 seconds), 3/4" - 1 1/4" (4-8 seconds), 1 1/2" - 2 1/2" (8-10 seconds)