Operator`s manual

Fig. 13: Programmable
Engine Exerciser
Fig. 10: Strip Heater Kit
(Accessory 44G)
series 300 ATS Optional Accessories
Accessory 1UP
UPS back up power to allow controller to run with LCD display
for 30 seconds without AC power
Accessory 11BE Feature Bundle Consists of:
A fully programmable engine exerciser with seven
independent routines to exercise the engine generator, with
or without loads, on a daily, weekly, bi – weekly or monthly
basis. Engine exerciser setting can be displayed and changed
from the user interface keypad.
Event Log display shows the event number, time and date
of event, event type, and event reason (if applicable).
A maximum of 300 events can be stored.
RS 485 Communications Port Enabled
Common Alarm Output Contact
Accessory 18RX
Relay expansion module (REX) provides for some commonly
used accessory relays, includes one form C contact for source
availability of normal (18G), and one contact for availability of
emergency (18B) (contact rating 5 amps @ 30Vdc or @125
Vac resistive). Additional output relay is provided, the default
is to indicate a common alarm. (See operator’s manual for
configurable options).
Accessory 23GA
1
(Single Phase),
and 23GB (Three Phase)
Load current metering card, measures either single or three
phase load current
Note1: This feature is not available with a Power Meter Option (135L)
Accessory 14AA/14BA
Auxiliary contacts to indicate position of main contacts. Two
(2) for normal and two (2) for emergency position (one set is
standard).
Accessory 44A
Strip Heater with thermostat for extremely cold areas to
prevent condensation and freezing of this condensation.
External 120 volt power source required.
Accessory 44G
Strip Heater with thermostat, wired to load terminals:
208-240, 360-380, 460-480, 550-600 volts. Contains wiring
harnesses for all transfer switch sizes.
8
Field Conversion Kits for
series 300 Transfer Switches
Kit No. Description
935147 Feature Bundle Includes Engine Exerciser/Event Log/RS 485/
Common Alarm Output Contact (Acc. 11BE) Dongle
935148 REX Module with Source Availability Contacts (Acc. 18RX)
935149 UPS to allow controller to run for 3 minutes minimum
without AC Power (Acc. 1UP)
935150 1/3 Phase load current sensing card only (Acc. 23GA/GB)
K613127-001 Strip Heater (125 watt) 120 volt (Acc.44A)
K613127-002 Strip Heater (125 watt) 208 - 480 volt (Acc.44G)
948551 Quad - Ethernet Module (Acc. 72EE)
K609027 Cable Pull Box (1600 - 2000 amp)
Accessory 72EE
Connectivity Module, enabling remote monitoring and
control capabilities (Pages 12-14)
Accessory 31Z
Selective load disconnect circuit to provide a pre transfer
and/or post transfer signal when transferring from emergency
to normal and/or normal to emergency.
Accessory 73
Surge Suppressor (TVSS) Rated 65kA
Accessory 62W
Audible alarm with silencing feature to signal each time switch
transfers to emergency (City of Chicago requirement)
Accessory 37B
6’ Extension harness for units shipped open type to
accommodate customer mounting of controls and switch
Accessory 37C
9’ Extension harness for units shipped open type to
accommodate customer mounting of controls and switch
Accessory 135L
2
Power Meter on load side (Includes shorting block and CT’s)
Note2: This feature is not available with Load Current Metering
Option (23GA, or 23GB)
Accessory 30AA
3
Load – shedding circuit initiated by opening of a customer –
supplied contact
Accessory 30BA
3
Load – shedding circuit initiated by removal of customer –
supplied voltage (* Specify voltage)
Note3: Accessory 30AA, and 30BA are only available for
3ADTS/3NDTS (Delayed Transition Transfer Switch)
Fig. 11: Relay Expansion
Module (Accessory 18RX)
Fig. 12: Load Current
Card (Accessory 23GA/GB)
Fig. 14: Accessory 1UP
UPS Backup Power