INSTALLATION (continued)
1--3
Controller Ground
A grounding wire must be connected to the controller’s
lower left mounting stud. Be cause the controller is
mounted on the enclosure door, a conductive strap must be
used between the enclosure and t he door. This connection
provides proper grounding which does not rely upon the
door hinges.
Harnesses
The transfer switch is connected to the left side of the
controller by a plug–in harness (two plugs).
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on
transfer switch. Note the control features that are fur-
nished on this switch. Make the necessary auxiliary
connections by referring to Section 5, Control Features.
Functional Test
The Functional Test consists of three checks: manual
operation, voltage checks, and electrical operation.
Do these checks i n the order presented to
avoid damaging the automatic transfer switch.
!
Read all instructions on the Wiring Diagram and labels
affixed to the automatic transfer switch. Note the control
features that are provided and review their operation
before proceeding.
1 – Manual Operation Test
A manual oper ator handl e (detachab l e on 225 – 400 amp.
sizes) is provided on the Transfer Switch for maintenanc
e
purposes only
. Manual operation of the transfer switch
should be checked before it is energized (operated
electrically).
Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
!
1. Select the appropriate switch amperage size / design
and follow the directions for installing the ha ndle:
30, 70, and 104 amp. B–design
and 150 and 200 amp. C–design See Figure 1-6.
Grasp attached manual handle (left side of the
operator) and turn it with thumb and fingers.
225, 260, and 400 amp. E–design SeeFigure1-7.
Insert the manua l handle into the hole in the shaft, left
side of the operator.
Figure 1-6. Attached maintenance
handle on 30, 70, and 104 amp.
B–design and 150 and 200 amp.
C–design transfer switches
Figure 1-7. Removable
maintenance handle on
225, 260, and 400 amp.
E–design switches
2. Movethehandleasshowntomanuallyoperatethe
transfer switch. The switch should operate smoothly
with out any binding . If it does not, che ck for shipp ing
damag e or c onstru ction debris.
3. Return the transfer sw itch to the N (normal) position.
4. R emove the manual operator handle (if detachable) and
store it on the transfer switch in the place provided.
Verify that the maintenance handle has
been removed (225–400 amp. size transfer
switches) before proceeding!
!
Now continue to 2–VoltageCheckson next page.