Specifications

SVI Trucks
Freightliner 4-Door Demo
SVI #917 01/05/15
77
Wiring System Components
Only stranded copper conductors with an insulation rated for temperatures of at least 194°F (90°C) and wet
locations shall be used. Conductors in flexible cord shall be sized in accordance with Table 400.5(A) of NFPA 70.
Conductors used in conduit shall be sized in accordance with 310.15, “Ampacities for Conductors Rated 02000
Volts,” of NFPA 70. Aluminum or copper-clad aluminum conductors shall not be used.
All boxes shall conform to and be mounted in accordance with Article 314, “Outlet, Device, Pull, and Junction
Boxes; Conduit Bodies; Fittings; and Manholes,” of NFPA 70. All boxes shall be accessible using ordinary hand
tools. Boxes shall not be permitted behind welded or pop-riveted panels.
The maximum number of conductors permitted in any box shall be in accordance with 314.16, “Number of
Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies,” of NFPA 70.
All wiring connections and terminations shall provide a positive mechanical and electrical connection. Connectors
shall be installed in accordance with the manufacturer’s instructions. Wire nuts or insulation displacement and
insulation piercing connectors shall not be used.
Each switch shall indicate the position of its contact points (i.e., open or closed) and shall be rated for the
continuous operation of the load being controlled. All switches shall be marked with a label indicating the function
of the switch. Circuit breakers used as switches shall be “switch rated” (SWD) or better. Switches shall
simultaneously open all associated line voltage conductors. Switching of the neutral conductor alone shall not be
permitted.
Line voltage circuits controlled by low voltage circuits shall be wired through properly rated relays in listed
enclosures that control all non-grounded current-carrying conductors.
Receptacles and Inlet Devices
Wet and Dry Locations
All wet location receptacle outlets and inlet devices, including those on hardwired, remote power distribution
boxes, shall be of the grounding type, provided with a wet location cover, and installed in accordance with Section
406.8, “Receptacles in Damp or Wet Locations,” of NFPA 70.
All receptacles located in a wet location shall be not less than 24 in. (600 mm) from the ground. Receptacles on
off road fire apparatus shall be a minimum of 30 in. (750 mm) from the ground. All receptacles located in a dry
location shall be of the grounding type and shall be at least 12 in. (300 mm) above the interior floor height. No
receptacle shall be installed in a face-up position.
The face of any wet location receptacle shall be installed in a plane from vertical to not more than 45 degrees off
vertical.
Receptacle Label
Each receptacle shall be marked with a label indicating the nominal line voltage (120 volts or 240 volts) and the
current rating in amps of the circuit. If the receptacle is DC or other than single phase, that information shall also
be marked on the label.
All receptacles and electrical inlet devices shall be listed to UL 498, Standard for Safety Attachment Plugs and
Receptacles, or other recognized performance standards.
Receptacles used for DC voltages shall be rated for DC service.