Specifications

SVI Trucks
Freightliner 4-Door Demo
SVI #917 01/05/15
76
Wiring Methods
Fixed wiring systems shall be limited to the following:
1) Metallic or nonmetallic liquid tight flexible conduit rated at temperatures not less than 194°F (90°C) with
stranded copper wire rated for wet locations and temperatures not less than 194°F (90°C)
2) Type SOW, SOOW, SEOW, or SEOOW flexible cord rated at 600 V and at temperatures not less than 194°F
(90°C)
Electrical cord or conduit shall not be attached to chassis suspension components, water or fuel lines, air or air
brake lines, fire pump piping, hydraulic lines, exhaust system components, or low voltage wiring and shall be
arranged as follows:
1) Separated by a minimum distance of 12 in. (300 mm) from exhaust piping or shielded from such piping
2) Separated from fuel lines by a minimum distance of 6 in. (150 mm)
A means shall be provided to allow “flexing” between the driving and crew compartment, the body, and other
areas or equipment whose movement would stress the wiring.
Electrical cord or conduit shall be supported within 6 in. (150 mm) of any junction box and at a minimum of every
24 in. (600 mm) of run.
Supports shall be made of nonmetallic materials or of corrosion-resistant or corrosion-protected metal. All
supports shall be of a design that does not cut or abrade the conduit or cord and shall be mechanically fastened
to the apparatus.
Only fittings and components listed for the type of cord or conduit being installed shall be used.
Splices shall be made only in a listed junction box.
Additional Requirements for Flexible Cord Installations
Where flexible cord is used in any location where it could be damaged, it shall be protected by installation in
conduit, enclosures, or guards.
Where flexible cord penetrates a metal surface, rubber or plastic grommets or bushings shall be installed.
Wiring Identification
Each line voltage circuit originating from the main panel board shall be identified.
The wire or circuit identification either shall reference a wiring diagram or wire list or shall indicate the final
termination point of the circuit.
Where pre-wiring for future power sources or devices exists, the un-terminated ends shall be marked with a label
showing their wire size and intended function.