Specifications
ST. PETERSBURG FIRE & RESCUE
AIR / LIGHT APPARATUS
SVI #865 PRODUCTION SPECIFICATION
SVI #865 04/26/13
64
GENERATOR MONITORING PANEL
To properly monitor the generator performance and load demand during operation, the generator installation shall be
equipped with a full instrument monitor panel.
• Generator frequency in hertz
• Line 1 current in amperes
• Line 2 current in amperes
• Generator voltage in volts
The program shall support the accumulation of elapsed generator hours. Generator hours shall be displayed.
SHORE POWER INLET - BATTERY CHARGER
The above mentioned shore power inlet, and battery conditioner shall be specified in the 12 volt section.
LINE VOLTAGE ELECTRICAL SYSTEM
GENERAL REQUIREMENTS
Stability
Any fixed line voltage power source producing alternating current (ac) shall produce electric power at 60 Hz, ±3 Hz when
producing power at all levels between no load and full rated power. Any fixed line voltage power source shall produce
electric power at the rated voltage ±10 percent when producing power at all levels between no load and full rated power.
The maximum voltage supplied to portable equipment shall not exceed 275 volts to ground. Higher voltage shall be
permitted only when used to operate fixed wired, permanently mounted equipment on the apparatus.
Conformance with National Electrical Code
All components, equipment, and installation procedures shall conform to NFPA 70, National Electrical Code, except where
superseded by the requirements of this chapter. Where the requirements of this chapter differ from those in NFPA 70, the
requirements in this chapter shall apply.
Where available, line voltage electrical system equipment and materials included on the apparatus shall be listed and
used only in the manner for which they have been listed. All equipment and materials shall be installed in accordance with
the manufacturer’s instructions.
Location Ratings
Any equipment used in a dry location shall be listed for dry locations. Any equipment used in a wet location shall be listed
for wet locations.
Any equipment, except a PTO-driven generator, used in an underbody or under chassis location that is subject to road
spray shall be either listed as Type 4 or mounted in an enclosure that is listed as Type 4.
If a PTO-driven generator is located in an underbody or under chassis location, the installation shall include a shield to
prevent road spray from splashing directly on the generator.