Specifications
ST. PETERSBURG FIRE & RESCUE
AIR / LIGHT APPARATUS
SVI #865 PRODUCTION SPECIFICATION
SVI #865 04/26/13
10
3. LOW VOLTAGE ALARM TEST
The following test shall be started with the engine off and the battery voltage at or above 12 V for a 12 V nominal system,
24 V for a 24 V nominal system or 36 V for a 42 V nominal system.
With the engine shut off, the total continuous electrical load shall be activated and shall continue to be applied until the
excessive battery discharge alarm activates. The battery voltage shall be measured at the battery terminals.
The test shall be considered a failure if the alarm does not sound in less than 140 seconds after the voltage drops to
11.70 V for a 12 V nominal system, 23.4 V dc for a 24 V nominal system, or 35.1 V for a 42 V nominal system.
The battery system shall then be able to restart the engine. Failure to restart the engine shall be considered a test failure.
LOW VOLTAGE - ELECTRICAL SYSTEM PERFORMANCE TEST
DOCUMENTATION
The manufacturer shall deliver the following with the fire apparatus:
1. Documentation of the electrical system performance tests
2. A written electrical load analysis, including the following:
a. The nameplate rating of the alternator
b. The alternator rating
c. Each of the component loads specified that make up the minimum continuous electrical load
d. Additional electrical loads that, when added to the minimum continuous electrical load, determine the total
continuous electrical load
e. Each individual intermittent electrical load
UL 120/240 VAC CERTIFICATION
The 120/240 volt electrical system shall be third-party, independent, audit-certified through Underwriters Laboratory (UL)
to the current edition of NFPA 1901 to perform as listed below;
The prime mover shall be started from a cold start condition, and the unloaded voltage and frequency shall be recorded.
The line voltage electrical system shall be loaded to at least 100% of the continuous rated wattage stated on the power
source specification label. Testing with a resistive load bank shall be permitted.
The power source shall be operated in the manner specified by the apparatus manufacturer as documented on instruction
plates or in operation manuals. The power source shall be operated at a minimum of 100% of the continuous rated
wattage as stated on the power source specification label for a minimum of two (2) hours.
The load shall be adjusted to maintain the output wattage at or above the continuous rated wattage during the entire 2-
hour test.










