SENSO8 LoRaWAN IAQ Sensor User Guide
SENSO8 LoRaWAN IAQ Sensor User Guide Table of Contents Introduction ............................................................................................................................. 3 Sensor Setup ............................................................................................................................ 3 Installation............................................................................................................................... 4 Operating Instruction ...........
SENSO8 LoRaWAN IAQ Sensor User Guide Introduction SENSO8 LoRaWAN IAQ Sensor is an LPWAN wireless indoor air quality sensor which can detect indoor temperature, humidity, and a wide range of gases like carbon dioxide, ammonia and hydrogen sulfide. The sensor reads the environment data and uploads the data to the LoRaWAN server with a simple, open API. The user guide is applicable for the SENSO8 LoRaWAN IAQ Sensor models: LRS10701-xxxx Sensor Setup 1.
SENSO8 LoRaWAN IAQ Sensor User Guide 3. Connect the wires connecting to the DC power supply to the terminal block on the bottom of the sensor or insert two ER26500 Li-SOCl2 batteries into the battery compartment. 4. Put on the cover and fasten the screws on the corners. 5. If DC supply is used, connect the wires from the terminal block a DC power supply, the LED indicator on the top cover will light up. For battery powered models, press and hold the button on the side for 3 seconds to power on the sensor.
SENSO8 LoRaWAN IAQ Sensor User Guide SENSO8 Sensor body Base 4. Slide the sensor main body down until it is locked to the base. SENSO8 Sensor body Base 5. Lock the sensor main body with a screw. 6. Power on the sensor i. Plug the DC adaptor to the AC main, the sensor will power on automatically on DC supply (for DC supply models), OR Rev. 1.
SENSO8 LoRaWAN IAQ Sensor User Guide ii. Press the multi-function button for 3 seconds to power on the sensor (for battery operated models). 7. On power on, the sensor will publish a data report to the LoRaWAN server. Check the server backend or dashboard to make sure the connection has been established and data can be successfully uploaded. Operating Instruction Power On For DC supply models, the sensor powers on automatically when connected to the power supply.
SENSO8 LoRaWAN IAQ Sensor User Guide Sensor Operation The sensor performs a sensor measurement every minute in the background. If the reading exceeds either one of the thresholds, the sensor will send an uplink data to the network server immediately with the corresponding alert. Otherwise, the sensor will go back to sleep mode. When the data upload interval is reached, the sensor will send an uplink data with the latest sensors’ reading.
SENSO8 LoRaWAN IAQ Sensor User Guide Carbon Monoxide Concentration Threshold 12400 ppb Nitrogen Dioxide Concentration Threshold 360 ppb PM2.5 Concentration Threshold 56 ug/m3 PM10 Concentration Threshold 254 ug/m3 LED ON/OFF Status ON - LED Indicator Device Status Event Powered On LED Pattern Blue LED on Powered Off Report Latest Data Blue LED flashes 3 times Blue LED on Description Device powered on, and uploading the first data.
SENSO8 LoRaWAN IAQ Sensor User Guide 101-150 Unhealthy for Sensitive Group 151-200 Unhealthy 201-300 Very Unhealthy 301-500 Hazardous Flashing Troubleshooting Guide Symptom The LoRaWAN network server cannot receive data from the sensor. Fix Check the configuration (activation mode, frequency plan, device info and all security key) on the LoRaWAN server and the sensor. If there is any mis-match, the data cannot be sent to the LoRaWAN network server.
SENSO8 LoRaWAN IAQ Sensor User Guide Regulatory Compliance Information FCC ID: 2AMWTLRS10701 MADE IN CHINA This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.