User Manual

32
Rev.13052022
505
540
1025
1045
important opening for ventilation
grille or ventilation holes
Model BBQ 60cm, 80cm100cm
The cylinder compartment must be ventilated in accordance
with AS/NZS 5601, (Appendix J - Clause J3 - 4: Cylinders in
an enclosure or recess), with the free ventilation area having
at least 20,000 squared mm at high and low level.
Cylinder compartments shall have permanent openings ventilating directly to outside and
consisting of either of the following:
(A) Perforations, uniformly distributed over the height of the enclosure and with a total free
area not less than 25% of the side wall area.
(B) Separate openings at a high and low level, such that –
(i) the total free area at high level is not less than 20,000mm² and is within 125mm on the
top of the cylinder compartment; and
(ii) the total free area at the low level is not less than 20,000mm², and –
(A) at least 25% of the required area is within 15mm of the base
of the cylinder compartment.
(B) the total required area is within 125mm of the base of the
cylinder compartment; and (C) the openings cannot be
obstructed by the cylinder(s)
Cylinder compartments shall have permanent openings
ventilating directly to outside and consisting of either of the following:
(A) Perforations, uniformly distributed over the height of the
enclosure and with a total free area not less than 25%
of the side wall area.
(B) Separate openings at a high and low level, such that –
(i) the total free area at high level is not less than
20,000mm² and is within 125mm on the top of the cylinder
compartment; and
(ii) the total free area at the low level is not less than
20,000mm², and –
(A) at least 25% of the required area is within 15mm of
the base of the cylinder compartment.
(B) the total required area is within 125mm of the base
of the cylinder compartment; and
(C) the openings cannot be
obstructed by the cylinder(s)
Cylinder compartments shall have permanent openings ventilating directly to outside and consisting
of either of the following:
(A) Perforations, uniformly distributed over the height of the enclosure and with a total free area not
less than 25% of the side wall area.
(B) Separate openings at a high and low level, such that –
(i) the total free area at high level is not less than 20,000mm² and is within 125mm on the top of the
cylinder compartment; and
(ii) the total free area at the low level is not less than 20,000mm², and –
(A) at least 25% of the required area is within 15mm of the base of the cylinder compartment.
(B) the total required area is within 125mm of the base of the cylinder compartment; and
(C) the openings cannot be obstructed by the cylinder(s)
OUTDOOR USE ONLY
540
830
505
800
important opening for ventilation
grille or ventilation holes
505
540
585
615
important opening for ventilation
grille or ventilation holes
Model BBQ 80 cm
Model BBQ 60 cm